46 / 136
00RNO0333-B (U0625869)
EVO S -
Installation and Servicing
E. SPECIFIC START-UP PROCEDURE
"
"
Make the accessories' electrical connections.
"
"
Start up the boiler only.
"
"
Make the following settings:
Line No. Value
• Configuration
menu
Boiler pump supplied by IDEAL
No adjustments necessary
Boiler pump supplied by the customer
(all-or-nothing control)
Relay output QX3
(5892) Boiler pump Q1
• Time and date
menu
Set the time
Hours / minutes
(1)
HH.MM
Set the date
Day / month
(2)
DD.MM
Set the year
Year
(3)
YYYY
For a request via 0...10V input
• Configuration
menu
Configure the H1 input
Function input H1
(5950)
Consumer request
VK1 10V
Voltage value 1 H1
(5953)
0.0
Function value 1 H1
(5954)
0
Voltage value 2 H1
(5955)
10.0
Function value 2 H1
(5956)
1000 (for equivalence
10 V = 100 °C)
Option: to keep the generator at a stop,
even if the 0...10V signal is different
from 0
Function input H5
(5977)
Inhibit starting
(produces a fault
E846)
For a request by LPB (
LPB network menu)
• LPB network
menu
Check that the boiler is defined as the
master generator
Device address
(6600)
1
Segment address
(6601)
0
Bus power supply function
(6604)
Automatically
Clock mode
(6640)
Slave with remote
setting
• Configuration
menu
Save the sensors
Save sensors
(6200)
Yes (switches back to
no automatically)
Diagram: VF1
page 3 / 4