68 / 136
00RNO0333-B (U0625869)
EVO S -
Installation and Servicing
Diagram: VF4
page 8 / 8
Line No. Value
•
Heating circuit 1 / 2 timer programme
menu
Preselection
Preselection
(500/520)
- - -
Adjust the timer programming
On / off phases
(501...506)
(521...526)
- - -
•
Heating circuit 1 / 2 holiday
menu
Preselection
Preselection
(641/651)
- - -
Adjust the timer programming
On / off phases
(642...-643)
(652-653)
- - -
• Switch the heating regime to automatic
AUTO
Maintenance optimisation on EVO S boiler:
A maintenance message may be generated that does not set the boiler to fault. This maintenance
message may be displayed after the following 3 counters have expired:
•
Time since last maintenance (or commissioning): set parameter 7044 to 12 months.
•
Operating hours of the burner (parameter 7040).
•
Number of starts (parameter 7042)
These last 2 parameters are dependent on the boiler's hydraulic installation. We recommend
using at least parameter 7044 for annual maintenance.
Ajusting the DWH (on the RVS 63):
• Timer prog. 4/DHW
menu
Adjust the programmed times
On/off phases
(561…566)
- - -
• DHW
menu
Adjust the low setpoint
Low setpoint
(1612)
- - -
Release the DHW load according to the
timer program
Release
(1620)
- - -
Adjust the frequency of the anti-
legionella cycle
Anti-legionella function
(1640)
- - -
Selon le réglage précédent, ajuster la
périodicité ou le jour de la semaine
Periodic legion. funct.
(1641)
- - -
or
Legionella funct weekday
(1642)
- - -
Adjust the anti-legionella cycle
temperature setpoint
Anti-legionella setpoint
(1645)
- - -
Adjust the duration of the anti-legionella
cycle
Anti-legionella function duration
(1646)
- - -
• DHW tank
menu
Adjust the primary rise/DHW
Rise in initial setpoint
(5020)
16 °C