E. D. SPECIFIC START-UP PROCEDURE
"
"
Make the accessories' electrical connections.
"
"
Start up the boiler only.
"
"
Make the following settings:
Line No. Value
•
Time and date
menu
Set the time
Hours / minutes
(1) HH.MM
Set the date
Day / month
(2) DD.MM
Set the year
Year
(3) YYYY
• Configuration
menu
Configure the alarm output
Relay output QX1
(5890)
Alarm output K10
Configure DHW pump Q3
Relay output QX2
(5891)
DHW ctrl elem Q3
• Configuration
menu
Save the sensors
Save sensors
(6200)
Yes (switches back
to no automatically)
•
Domestic hot water
menu
Adjust the comfort setting
Nominal setpoint
(1610) 55 °C
Adjust the DHW release mode
Release
(1620) 24/day
• Activate the DHW mode
F. ELECTRICAL AND HYDRAULIC VALIDATION
•
Inputs/outputs test
menu
Check the outputs
Alarm relay
Relay test
(7700)
Relay output QX1
DHW pump Q3
Relay test
(7700)
Relay output QX2
Reset the outputs
Relay test
(7700)
No test