MODEL
SYMBOL
UNITS
30
30P
40
40P
60
60P
Condensing Boiler
n/a
n/a
yes
yes
yes
yes
yes
yes
Low Temperature Boiler
n/a
n/a
no
no
no
no
no
no
B1 Boiler
n/a
n/a
no
no
no
no
no
no
Cogeneration Space Heater
n/a
n/a
no
no
no
no
no
no
Equipped with a Supplementary Heater
n/a
n/a
no
no
no
no
no
no
Combination Heater
n/a
n/a
no
no
no
no
no
no
Nominal Heat Output for Space Heating
Full Load
P
4
kW
30
30
40
40
60
60
Part Load
P
1
kW
9.7
9.7
13
13
19.5
19.5
Auxiliary Electricity Consumption
Full Load
el
max
kW
0.081
0.081
0.138
0.138
0.082
0.082
Part Load
el
min
kW
0.027
0.027
0.029
0.029
0.0251
0.0251
Standby
P
SB
kW
0.003
0.003
0.003
0.003
0.003
0.003
Seasonal Space Heating Energy Efficiency
Full Load
ƞ
4
%
89.6
91.6
89.6
91.5
89.7
91.7
Part Load
ƞ
1
%
98.4
99.6
97.8
99.5
97.9
99.7
Standby Loss
P
stby
kW
0.08
0.08
0.08
0.08
0.11
0.11
Ignition
P
ign
kW
0
0
0
0
0
0
Emissions
NO
x
mg/kWh
34.1
52.3
33.2
64.4
35.2
67.7
Annual Energy Consumption
Q
HE
GJ
93
91
124
121
186
182
Sound Power Level, Indoors
L
WA
dB
55.2
55.2
57.7
57.7
59
59