3.10 REMOVAL OF GAS VALVE
1. Refer to Section 2.33.
2. Remove the upper front panel (Refer to Section 3.2).
3. Remove the fan and gas assembly and air inlet damper
(Refer to Section 3.2).
4. Remove the 3 screws holding the gas valve to the venturi
(30,40,60,80 only).
5. Remove the venturi from the fan to access the gas valve
fixing screws (100, 120 & 150 only Refer to Section 3.9).
6. Remove the four screws retaining the gas valve (100, 120 &
150).
7. Remove the 4 screws retaining the inlet flange to gas valve
& transfer to new valve.
8. Fit new gas valve to venturi using the new seal provided,
ensure gas injector is fitted correctly.
9. Reassemble in reverse order replacing all gaskets.
10. Check the operation of the boiler.
11. Refer to Section 2.33.
8
8
8
8
8
30, 40 & 60kW
100kW
150kW
80kW
120kW
56
Installation & Servicing
SECTION 3 - SERVICING
SER
VICING
Summary of Contents for EVOMAX 2 30