28
UIN
DESCRIPTION
220925
Multiline Starter Kit 80/125
220926
Multiline Extension Kit 80/125
220927
Multiline Starter Kit 100/150
220928
Multiline Extension 100/150
EVOMAX MODEL OUT-
PUT
CASCADE SYSTEM LIMITS
COMBUSTION PRODUCTS DATA
Model
Maximum
System
Capacity
Maximum
Permissible Header
Pressure ‘A’
(Static)
Max rate
CO
₂
Min rate
CO
₂
Temperature
Max
Max
Min
Hmax
Pmax
±
0.5
±
0.5
kW
kW
kW
Pa
%
%
C
30
7.5
400
40
9.7
9.0
72
40
10
60
15
80
20
100
25
600
80
120
30
150
37.5
30P
7.5
400
40
11.4
10.6
40P
10
60P
15
80P
20
At the maximum system capacity the static
pressure generated against the flue resistance
at position [A] must not exceed the value Pmax
quoted in the table below.
*
Multiline flue supplied to point A.
Customers are to fabricate / supply B
type flue system to termination point
within flue resistance parameters.
Flue height = 570mm from the top of the first boiler in the system.
Increase the height 29mm for each adjacent boiler.
Customer specified
components*
Must be CE approved
A*
A*
3.0ºC
Condensate Drain
(Siphon)
Header