21 EXAMPlES OF CAlCUlATING FlUE RESISTANCES/lENGTHS - EXAMPlE 3
The maximum flue extension for an Evomax 30 on open flue is 65m. Therefore
this installation is acceptable.
Example 3
22 EXAMPlES OF CAlCUlATING FlUE RESISTANCES/lENGTHS - EXAMPlE 4
The total maximum flue resistance for an Evomax 120 is 288 Pa or
17.6m 100/150. Therefore this installation is acceptable.
Example 4
FLUE OUTLET
Horizontal Flue for Evomax 120
Resistance (Pa) Resistance (m)
Flue Size
100/150
100/150
Horizontal Wall Flue Kit 100/150
100
3.3
2 x 1m extension flue
2 x (16.4)
2 x (1)
1 x 90º elbow
50
2
Total Flue Resistance
183
7.3
Open Flue for Evomax 30
Resistance (m)
Flue Size
80
5 x 1m extension
5 x 1
2 x 45º elbow
2 x 0.6
Total Flue Resistance
6.2