2
Falcon GTE -
Installation & Servicing
GENERAL
Note
.
Fuel rates and flue gas data relate to maximum output ratings.
Gas firing data relates to the use of NATURAL GAS ONLY.
Details for the use of LPG are available on request from Caradon
Ideal Ltd.
Natural gas consumption is calculated using a calorific value of
38.7MJ/m
3
(1038Btu/ft
3
) gross or 34.9MJ/m
3
(935Btu/ft
3
) nett at
15
o
C and 1013.25mbar.
Oil rates relate to Gas Oil using a calorific value of 45.56 MJ/kg
gross or 42.69 MJ/kg nett.
Table 1 Performance Data
Boiler
GTE 4
GTE 5
GTE 6
GTE 7
GTE 8
Number of Sections
4
5
6
7
8
Maximum
kW
50
64
78
92
102
Heat Ouptut
Btu/hx10
3
170
218
266
314
348
Minimum
kW
36
50
64
78
92
Heat Output
Btu/hx10
3
123
170
218
266
314
Hydraulic
mbar
20.3
33.3
49.3
68.4
84.0
Resistance at 11k
in w.g.
8.1
13.3
19.7
27.4
33.6
Hydraulic
mbar
6.1
10.1
14.9
20.7
25.4
Resistance at 20k
in w.g.
2.5
4.0
6.0
8.3
10.2
Combustion Chamber
mbar
0.4
0.6
0.6
0.6
0.8
Resistance (at zero draught)
in w.g.
0.16
0.24
0.24
0.24
0.32
Minimum Draught at Smokehood mbar
0
0
0
0
0
Outlet (for max. output)
in w.g.
0
0
0
0
0
HEALTH & SAFETY DOCUMENT NO. 635
The electricity at work regulations, 1989
. The manufacturer's
notes must NOT be taken, in any way, as overriding statutory
obligations.
IMPORTANT
. These appliances are CE certified for safety and
performance. It is, therefore, important that no external control
devices, e.g. flue dampers, economisers etc., are directly
connected to these appliances unless covered by these
Installation and Servicing Instructions or as otherwise
recommended by
Caradon Ideal Limited
in writing. If in doubt
please enquire.
Any direct connection of a control device not approved by
Caradon Ideal Limited
could invalidate the certification and the
normal appliance warranty. It could also infringe the Gas Safety
Regulations and the above regulations.
Maximum Gross
l/h
5.61
7.18
8.80
10.38
11.51
Oil Rate
gal/h
1.23
1.58
1.93
2.27
2.52
Maximum Flue
m
3
/s
0.031
0.040
0.049
0.058
0.064
Gas Volume
ft
3
/min
66
85
104
123
136
Flue Gas CO
2
/ Temperature
% /
o
C
12 / 200
12 / 200
12 / 200
12 / 200
12 / 200
Oil
Maximum
m
3
/h
5.58
7.16
8.78
10.33
11.48
Gas Rate
ft
3
/h
197.5
252.8
309.8
365.4
405.1
Maximum Flue
m
3
/s
0.032
0.042
0.051
0.061
0.067
Gas Volume
ft
3
/min
69
89
109
128
142
Flue Gas CO
2
/ Temperature
% /
o
C
9 / 200
9 / 200
9 / 200
9 / 200
9 / 200
Gas
Table 2 General Data
Flow Connection
R 1
1
/
4
"
R 1
1
/
4
"
R 1
1
/
2
"
R 1
1
/
2
"
R 1
1
/
2
"
Return Connection
R 1
1
/
4
"
R 1
1
/
4
"
R 1
1
/
2
"
R 1
1
/
2
"
R 1
1
/
2
"
Maximum Operating Pressure
bar
4
4
4
4
4
Boiler Thermostat Setting
o
C
30-90
30-90
30-90
30-90
30-90
Safety Thermostat Setting
o
C
110
110
110
110
110
Nominal Flue
m m
153
153
180
180
180
Diameter
in.
6
6
7
7
7
Boiler Water
l
36
43
50
57
64
Content
gal
7.9
9.5
11.0
12.5
14.1
Boiler DRY Weight
kg
254
295.5
343.5
380.5
422.5
less Burner Unit
lb
560
651.5
757.5
839
931.5