background image

FP14KC-X 

JAN 2023

 

Foundation & Anchoring Requirements: 

 

1. 

Concrete shall have compression strength of at least 3,000 PSI and a minimum thickness of 4-1/4

” in order 

to achieve a minimum anchor embedment of 3-1/4

”.  NOTE: When using the standard supplied 3/4” x 5-1/2” 

long  anchors,  if  the  top  of  the  anchor  exceeds  2-1/4

”  above  the  floor  grade,  you  DO  NOT  have  enough 

embedment.  

2. 

Maintain a 6

” minimum distance from any slab edge or seam.  Hole to hole spacing should be a minimum 6-

1/2

” in any direction.  Hole depth should be a minimum of 4-1/4”.  

3. 

DO NOT install on asphalt or other similar unstable surface.  Columns are supported only by anchoring to 
floor.  

4. 

Using the horseshoe shims provided, shim each column base as required until each column is plumb. If one 
column has to be elevated to match the plane of the other column, full size base shim plates should be used. 
Torque anchors to 130 ft-lbs.  Shim thickness MUST NOT exceed 1/2

” when using the 5-1/2” long anchors 

provided with the lift.  

5. 

If anchors do not tighten to 130 ft-lbs. installation torque, replace the concrete under each column base with 
a 2

’ x 2’ x 6” thick 3,000 PSI minimum concrete pad keyed under and flush with the top of existing floor.  Allow 

concrete to cure before installing lifts and anchors (typically 2 to 3 weeks). 

 

Anchoring Tips 

 

1. 

Use a concrete hammer drill with a carbide tip, solid drill bit the same diameter as the anchor, 3/4

” (.775 

to .787 inches diameter).  Do not use excessively worn bits or bits which have been incorrectly sharpened.  

2. 

Keep the drill in a perpendicular line while drilling.  

3. 

Let the drill do the work. Do not apply excessive pressure.  Lift the drill up and down occasionally to remove 
residue to reduce binding. 

4. 

Drill the hole to depth of 2

” deeper than the length of anchor.  NOTE: Drilling thru concrete (recommended) 

will allow the anchor to be driven thru the bottom of foundation if the threads are damaged or if the lift will 
need to be relocated.  

5. 

For better anchoring holding power, blow dust from the hole. 

6. 

Place a flat washer and hex nut over threaded end of anchor, leaving the nut almost flush with the top of the 
anchor bolt. Carefully tap anchor into hole. Do not damage threads.  Tap anchor into the concrete until nut 
and flat washer are against base plate.  Do not use an impact wrench to tighten!  Tighten the nut, two or 
three turns on average after the concrete has cured (28-day cure).  If the concrete is very hard only one or 
two turns may be required. 

 

 

Drill holes using 3/4” 

  Clean hole.   

Run nut down just  

Tighten nut with 

carbide tipped 

 

below impact section  

Torque wrench to 

masonry drill bit per 

 

of bolt. Drive anchor  

130 ft.-lbs. 

ANSI standard 

 

into hole until nut and  

 

B94.12.1977 

 

washer contacts base.  

 

Summary of Contents for FP14KC-X

Page 1: ...hicle Lift 14 000 lb Capacity Installation Operation Manual IMPORTANT READ THIS MANUAL THOROUGHLY BEFORE INSTALLING OPERATING OR MAINTAINING THIS LIFT WHEN DONE WITH INSTALLATION BE SURE TO RETURN DOC...

Page 2: ...lation Instructions Pages 9 21 Lift Location Runway Crossbeam Post Crossbeam Anchoring Posts Power Unit Control Bracket Hydraulic Hose Airline Power Unit Electrical Connection Cycle Testing Bleeding H...

Page 3: ...ould not wear loose clothes to avoid being clamped by any moving part when the machine is descending or rising Area around the lift must be kept clean to help avoid accidents and possible lift malfunc...

Page 4: ...on Lift Description The iDEAL FP14KC X 14 000 lb Four Post Commercial Service Lift is a high performance closed front cable pull vehicle lift designed for Cars SUVs Vans Trucks The FP14KC X Service Li...

Page 5: ...5 FP14KC X JAN 2023 Lift Layout Fig 1...

Page 6: ...r trailer The four post lift package alone weighs close to 2 700 pounds not including any kits or optional accessories that may be included Un banding the Lift The steel bands which secure the lift pa...

Page 7: ...where the lift is to be installed and check for cracked or defective concrete This lift must be installed on a solid level concrete floor with no more than 2 degrees of slope A level floor is suggeste...

Page 8: ...anchors typically 2 to 3 weeks Anchoring Tips 1 Use a concrete hammer drill with a carbide tip solid drill bit the same diameter as the anchor 3 4 775 to 787 inches diameter Do not use excessively wor...

Page 9: ...e adequate clearance around the lift s outer perimeter for safety clearance as shown in Fig 3 Ensure concrete floor is level meets Foundation Anchoring Requirements on Page 8 NOTE The Main Side Power...

Page 10: ...ay making sure the hydraulic hose connection is positioned to the front of bay Fig 4 Fig 4 2 Pull cable ends air tubing and hydraulic lines out from the ends of the Main Side Runway for assembly Ensur...

Page 11: ...aside for reassembly in the follwing steps Fig 6 6 Slide the cables from the ends of power side runway and route the cables though the crossbeams referring to the routing diagram in Fig 7 Fig 7 CAUTI...

Page 12: ...s and the holes in the front wheel stops Secure runway wheel stop to the crossbeam using four M12 x 40mm hex flange bolts Fig 9 Fig 9 9 Bolt the rear of runways onto the rear crossbeam by aligning the...

Page 13: ...inserted through the outer top plate hole for each Post 4 Carefully position each Post to be centered around the Crossbeam ends while still allowing the Nylon Slider bolt holes to stay exposed Bolt S...

Page 14: ...the Slack Cable Roller 7 Locate the Plastic Crossbeam Covers and mount to the top of each Crossbeam ends using the Plastic Insert Screws Fig 14 8 Re install Cable Guide Tabs to the underside of each...

Page 15: ...are damaged or if the lift will need to be relocated 3 After drilling remove dust thoroughly from each hole using compressed air and or wire brush Make certain that the column remains aligned with the...

Page 16: ...t Fig 20 Fig 21 2 Mount Control Bracket to the backside of the Main Side Post Bracket s left side while using the same M8 x 25mm Bolts M8 Washers Hex Nuts to mount the Power Unit Fig 20 Ensure to tigh...

Page 17: ...h Corrugated Flex Tubing already attached Gently pull hose slack through the Flex Tubing Figs 23 24 Fig 23 Fig 24 4 Install 90 degree Power Unit Fitting to HP Port on left side of Power Unit shown in...

Page 18: ...rt A Figs 27 A B Fig 27 8 Connect D6 Airline to the Outlet Valve Port P and route through Flex Tubing to connect to T Fitting Connect airlines to each end of T Fitting then connect to Y Fittings in Cr...

Page 19: ...220VAC electrical supply to Power unit and connect shop air to Quick Disconnect Air Fitting on Control Bracket Ensure shop air supply to Air Fitting is between 90 115 PSI for proper Latch operation F...

Page 20: ...to the outside of the Runway Pivot Tubes Fig 31 Cable Leveling Adjustment 2 Adjust cable s with lift fully lowered and with Crossbeams touching Base Plates Loosen top jam nut and tighten nut on cable...

Page 21: ...tment nuts on cable end or latch bar stud always leave at least two threads showing between top nut and stud end Be sure all four corners have passed the locking latch bar slot before lowering lift on...

Page 22: ...capacity Never allow unauthorized persons to operate lift Thoroughly train new persons employees in the use operation and care of lift Prohibit unauthorized persons from being in shop area while lift...

Page 23: ...t the latches set tight in a lock position Never work under a lift that is not in the locked position at all four corners of lift WARNING Always have the Lift in the Locked Position before going under...

Page 24: ...her of Power Unit 1 Oil reservoir tank overfilled Relieve all pressure and siphon out hydraulic fluid until at a proper level 2 Lift lowered too quickly while under a heavy load Lower the lift slowly...

Page 25: ...1 Locate the check valve the flush plug to the left of the lowering valve Step 2 Using an Allen wrench and shop towel with shop towel in place to catch fluid loosen the check valve plug 2 turns to al...

Page 26: ...sually while in operation Check safety latches for free movement and full engagement with latch rack Check hydraulic connections and hoses for leakages Check cables anchoring connections for cracks an...

Page 27: ...27 FP14KC X JAN 2023 Exploded Views Structure...

Page 28: ...28 FP14KC X JAN 2023...

Page 29: ...29 FP14KC X JAN 2023...

Page 30: ...021 TT 8861 200 01 HJ Latch Rack 4 22 FP14KCX 022 GB95 1985 D8 Flat Washer D8 4 23 FP14KCX 023 GB70 1 2000 M8 12 Screw M8 x 12mm 4 24 FP14KCX 024 TT 8861 100 01B HJ Slack Cable Latch LH 4 25 FP14KCX 0...

Page 31: ...072 GB70 2 2000 M10X25 Screw M10 x 25mm 4 73 FP14KCX 073 TT 8861 300 09 Rubber Grommet Runway 2 74 FP14KCX 074 GB T91 2000 5X40 Split Pin 5mm x 40mm 1 75 FP14KCX 075 8045 401G Cylinder Connector 1 76...

Page 32: ...32 FP14KC X JAN 2023 Exploded View Power Unit PU 220V FP14KCX...

Page 33: ...200 E00 Reservoir Fill Cap 1 19 PU 220V FP14KCX 019 5901 01120 355 O Ring D112 x 3 55mm 1 20 PU 220V FP14KCX 020 5105 08080 000 Hex Socket Bolt M8 x 80mm 2 21 PU 220V FP14KCX 021 BZ01 00001 100 Return...

Page 34: ...considered a warranty issue and therefore must be noted for any potential recovery with the shipping company The customer is required to notify Tuxedo of any missing parts within 72 hours Timely notif...

Reviews: