6
Harrier GTE -
Installation & Servicing
GENERAL
1
BOILER DIMENSIONS
2
BOILER CLEARANCES
796
D
A
L
P
195
105
Rp 1
1
/
2
draining outlet
(supplied with plug)
2
1
/
2
heating flow
( counter flange)
Rp 2
1
/
2
heating return
( counter flange)
Rp 2
1
/
2
diameter sludge
removal hole
C
B
398
398
594
101
101
1
1
9
2
387
137
8
2
7
10
1
7
137
Ø
R
153
153
53
H
har5963
1
1
5
Rp 1
1
/
2
for safety
relief valve
only
har5
964
B
1,192m
1m
1,5
m
A
0,795m
see notes
The minimum dimensions as indicated must be
respected to ensure good access around the boiler.
Note.
To allow the inlet of the combustion air, the boiler
room must be adequately ventilated, the section and the
location of which must comply with local
recommendations.
Refer also to Frame 3.
The boiler must be positioned so that there is enough
space available to allow the following:
•
Access around the boiler for servicing.
•
Space to open the boiler front door.
•
Space to access the burner.
Recommended minimum clearances are as shown.
Rear 1000mm or adequate space to make the flue
connections and access to the flue sample point,
drain connection, flue and smokehood cleanout
doors and any safety or control devices.
Sides One side may be 100mm the other side must be
200mm plus the burner projection or 500mm
whichever is the greater to allow the burner door to
be swung open and maintain access to the rear.
In multiple boiler installations both sides may be
100mm except at one end consideration must also
be given to the burner door hinge position and
consequent clearance for access to the rear.
Boiler
GTE 5
GTE 6
GTE 7
GTE 8
GTE 9
Standard
A
130
130
130
130
130
Control
B
105
105
105
105
105
Panel
C
165
165
165
165
165
Fitted
D
738
738
738
738
738
H
1297
1297
1297
1297
1297
Deluxe
A
355
355
355
355
355
Control
B
195
195
195
195
195
Panel
C
145
145
145
145
145
Fitted
D
755
755
755
755
755
H
1387
1387
1387
1387
1387
All
L
1151
1311
1471
1631
1791
Models
P
650
810
970
1130
1290
ØR
180
180
200
200
200
Dimension Boiler
GTE 5 GTE 6 GTE 7 GTE 8 GTE 9
A
m m
1000 1160 1320 1480 1640
B Standard Control Panel m m
105
105
105
105
105
Deluxe Control Panel
m m
195
195
195
195
195
For latest prices and delivery to your door visit MyTub Ltd - 0845 303 8383 - www.mytub.co.uk - info@mytub.co.uk