INSTALLATION
34
IMAX XTRA -
Installation & Servicing
Press
Display
Factory
Setting
Upper
Limit
Lower
Limit
Description
Booster time (minutes)
00 30 00
note 00 = Off
19
P19
CH flow parallel shift
00 80 10
For use with outside temperature sensor
20
P20
N/A
Do not Do not
20
adjust adjust
21
P21
Maximum fan speed CH
(hundreds)
E320
52
E400
52
E480 Do not Do not
55
E560 adjust adjust
55
P22
37 ADVANCED CONTROLS ACCESS CONT'D
. 0 0
. 1 0
. 2 0
22
. 4 8
. 0 0
. 4 8
23
24
Ignition fan speed
(hundreds)
E320
35
E400
25
E480 Do not Do not
25
E560 adjust adjust
25
. 3 5
28
P28
P23
Maximum fan speed CH
(units)
E320
00
E400
00
E480 Do not Do not
00
E560 adjust adjust
00
P24
Maximum fan speed DHW
(hundreds)
E320
52
E400
52
E480 Do not Do not
55
E560 adjust adjust
55
. 0 0
25
P25
Maximum fan speed DHW
(units)
E320
00
E400
00
E480 Do not Do not
00
E560 adjust adjust
00
. 1 2
26
P26
Minimum fan speed
(hundreds)
E320
18
E400
20
E480 Do not Do not
19
E560 adjust adjust
17
. 1 6
27
P27
Minimum fan speed
(units)
E320
00
E400
00
E480 Do not Do not
00
E560 adjust adjust
00
continued...........
29
P29
Fan speed during forced low time
(x100rpm)
E320
20
E400
20
E480 Do not Do not
20
E560 adjust adjust
20
. 1 6
INST
ALLA
TION