INSTALLATION
35
IMAX XTRA -
Installation & Servicing
DHW priority time over CH (secs)
0 120 30
0 = DHW always has priority
1-120 mins
The DHW has priority over CH until priority is switched back to CH.
Press
Display
Factory
Setting
Upper
Limit
Lower
Limit
Description
Forced low time
(x 9 seconds)
Do not Do not
6
adjust adjust
30
P30
Slow start
31
P31
CH post pump time
(minutes)
00 99 05
Note 0 = 10 seconds
Do not set below 05
. 0 5
32
P32
DHW post pump time
(x 10 seconds)
00
30
11
. 0 3
33
P33
CH modulation hysteresis on (
o
C)
Do not Do not 05
(Master)
adjust adjust 02
(Slave)
. 0 5
34
P34
CH modulation hysteresis off (
o
C)
Do not Do not 05
(Master)
adjust adjust 10
(Slave)
. 0 5
35
P35
DHW modulation hysteresis on (
o
C)
Do not Do not 03
(Master)
adjust adjust 02
(Slave)
. 0 5
36
P36
DHW modulation hysteresis off (
o
C)
Do not Do not 03
(Master)
adjust adjust 10
(Slave)
. 0 5
37
P37
. 0 3
. 0 3
. 0 0
. 0 0
Blocking time DHW to CH
(seconds)
0 30 05
0=switch with burner on
(x10.2 seconds)
. 0 0
. 2 5
38
39
40
41
42
43
P38
N/A
Do not Do not
03
adjust adjust
N/A
Do not Do not
03
adjust adjust
Blocking time CH
(seconds)
00 30 00
Minimum off period between CH demands to reduce cycling
Blocking time DHW
(seconds)
00 30 00
Minimum off period between DHW demands to reduce cycling
P39
P40
P41
P42
P43
continued...........
38 ADVANCED CONTROLS ACCESS CONT'D
TIME - Temp. differential between flow temp &
set point at which slow start ends.
0
15
10
TIME - Modulation rate in slow start X 400rpm/min
0
15
02
. 0 0
RMCI address
Do not Do not
00
Note -01=RMCI off
adjust adjust
44
P44
INST
ALLA
TION