FAULT FINDING
F
AUL
T FINDING F
AUL
T FINDING F
AUL
T FINDING F
AUL
T FINDING F
AUL
T FINDING F
AUL
T FINDING
53
IMAX XTRA -
Installation & Servicing
Code Description
Action
29
Incorrect tacho signal from fan
Check wiring to fan. If wiring OK replace fan.
30
Flow/return temperature differential too high
Check no air in system or boiler
Check adequate flow of water through boiler
31
Flow thermistor short circuit
Check wiring
Disconnect terminals from thermistor & confirm short
circuit using meter
Replace thermistor
32
Return thermistor short circuit
Check wiring
Disconnect terminals from thermistor & confirm short
circuit using meter
Replace thermistor
33
Tank sensor short circuit
Not fitted check parameter 46 settings
35
Flue thermistor short circuit
Check wiring
Disconnect terminals from thermistor & confirm short
circuit using meter
Replace thermistor
36
Flow thermistor open circuit
Check wiring
Disconnect terminals from thermistor & confirm open
circuit using meter
Replace thermistor
37
Return thermistor open circuit
Check wiring
Disconnect terminals from thermistor & confirm open
circuit using meter
Replace thermistor
38
Tank sensor open circuit
Not fitted check parameter 46 settings
40
Flue thermistor open circuit
Check wiring
Disconnect terminals from thermistor & confirm open
circuit using meter
Replace thermistor
44
Internal Failure
Check wiring harness & connections
If wiring OK replace control module
52
Flue gas temperature too high
Check no air in system or boiler
Check adequate flow of water through boiler
60
Error reading parameters
Press reset. If fault keeps re-occuring replace control module.
61
Air pressure switch closed when it should be open
Check for blockages in air pressure switch sensing pipes
Check air pressure switch and replace if necessary
107
Heat exchanger thermistor short circuit
Check wiring
Disconnect terminals from thermistor & confirm short
circuit using meter
108
Heat exchanger thermistor open circuit
Check wiring
Disconnect terminals from thermistor & confirm open
circuit using meter
Replace thermistor
109
Heat exchanger temperature too high
Check no air in system or boiler
Check adequate flow of water through boiler
110
Heat exchanger temperature too low
Check no air in system or boiler
Check adequate flow of water through boiler
111
Heat exchanger to return temperature differential too high
Check no air in system or boiler
Check adequate flow of water through boiler
112
Heat exchanger temperature rise too fast
Check no air in system or boiler
Check adequate flow of water through boiler
113
No valid mains frequency detected
Check power supply to boiler
114
Invalid or conflicting cascade address
Press reset. If fault keeps re-occuring replace control module.
115
Internal error
Check wiring harness & connections
If wiring OK replace control module
MASTER AND SLAVE BOILER CONTROL MODULE ERROR CODES CONTINUED