39
Installation & Servicing
INSTALLATION
INST
ALLA
TION
CHANGING THE SOFT START TIME
Installer Mode
Normal Operation
Set Flow Temp’
Set DHW Temp’
The Soft Start Time is the time for which the boiler will run at the ignition
rate after a flame is detected
This feature helps make the boiler fully compatible with the CH/DHW
system. The default Soft Start time is 5s
Care should be taken in adjusting this feature as system noise and/or
boiler lockout could occur
Press SELECT and then hold + and - down together for more than 5s,
the following screen will be displayed
Rotate the KNOB clockwise until the following screen is displayed
Installer Mode
Sys Frost Protect
Soft Start Time
O/S Room Temp’
DHW Sensor
Press SELECT and the following screen will be displayed
Soft Start Time
5s
Press + and - to change to required setting then press ENTER to store
Rotate the KNOB clockwise until Normal Operation is highlighted again
and press SELECT to return to normal operation
Note that the minimum setpoint after adjustment is 60s
ENABLING THE DOMESTIC HOT WATER THERMISTOR
Installer Mode
Normal Operation
Set Flow Temp’
Set DHW Temp’
The default is for a DHW Heat Demand to be indicated by a DHW
Thermostat providing a 230V input to the DHW Switched Live
Instead a DHW Thermistor, available as a kit from Ideal, can be
connected to the DHW Thermistor input
Rotate the KNOB clockwise until the following screen is displayed
Rotate the KNOB clockwise until the following screen is displayed
Installer Mode
O/S Room Temp’
DHW Sensor
Factory Settings
Anti-Legion Temp’
Press SELECT and the following screen will be displayed
DHW Sensor
Heating Only
DHW Thermistor
DHW Switched Live
Press + and - to change to the required setting and then press ENTER
to store
Rotate the KNOB clockwise until Normal Operation is highlighted again
and press SELECT to return to normal operation
continued . . . . . . . .
CHANGING THE NOMINAL ROOM TEMPERATURE ACHIEVED
DURING OUTSIDE SENSOR OPERATION (O/S ROOM TEMP’)
Installer Mode
Normal Operation
Set Flow Temp’
Set DHW Temp’
Note that the O/S Room Temp’ Function is only operational if an
Outside Sensor has been connected
The O/S Room Temp’ is the notional room temperature that the
boiler will try to achieve under Weather Compensation operation
The default O/S Room Temp’ is 20°C
Press SELECT and then hold + and - down together for more than
5s, the following screen will be displayed
Rotate the KNOB clockwise until the following screen is displayed
Installer Mode
Soft Start Time
O/S Room Temp’
DHW Sensor
Factory Settings
Press SELECT and the following screen will be displayed
O/S Room Temp’
20ºC
Press + and - to change to required setting, press ENTER to store
Rotate the KNOB clockwise until Normal Operation is highlighted
again and press SELECT to return to normal operation