25 CONNECTING ThE FLUE TO ThE BOILER
Notes.
• Before fitting the flue turret fill the condensate
trap within the boiler by pouring a cupful of
water into the flue outlet (shown below).
Take
care to ensure that the water is only poured into
the flue outlet, and does not spill into the boiler
casing.
• During assembly check that flue seals do not
become dislodged.
1.
Ensure front panel is removed.
Refer to Frame 9.
2.
Fit internal (white) & external (black)
flue seal onto flue & locate the flue
into the turret.
3.
Insert the flue assembly through
the prepared hole in the wall. Push
through and pull back to seal against
outside wall face. Push internal seal
against internal wall.
4.
Ensure rubber flue seal is present
& fully engaged into plastic top flue
manifold then locate the flue turret
into the flue manifold and secure by
applying downward pressure.
5.
Engage the clamp in its slide
mechanism and push it horizontally
backwards
6.
Locate BOTH plastic pegs BEFORE
the front retaining clip is fully located.
Note - Flues over 1 metre long
It is recommended that a support
bracket is fitted for every 1 metre of
extension pipe used and a bracket
should be used at every joint, to ensure
pipes are held at the correct angle.
2
3
204626-9847new
5
6
Plastic Pegs
(assembled)
Retaining Clip
(assembled)
3G9847e
Flue Outlet
4
10120-204626
noTe. siDe Flue
Select the orientation
before inserting turret into
boiler flue manifold.
DO NOT twist the turret
once inserted.