background image

4

Wiring Condition

Display Indication

H G N

Correct Wiring
No Ground
Polarity Reversal
Open/Hot Neutral
False Ground

If the wiring condition is other than normal, the SureTest is limited on its 
measurements that can be performed.  If a no ground condition exists, only the
line voltage and voltage drop measurements are available.  In a hot/ground rever-
sal, open neutral or open hot condition, the unit will not have any power so the
display will be blank.

Notes:

1)  Will not detect two hot wires in a circuit.
2)  Will not detect a combination of defects.
3)  Will not detect reversal of grounded and grounding conductors.

False Ground Indication

The SureTest indicates when a false ground condition exists from an improper bond
via a bootleg (ground jumper wire at the outlet device) or inadvertent contact of the
ground wire to the neutral connection. Note that if the SureTest is within 15-20 feet
of the main panel, the unit will indicate a false ground condition on a properly wired
circuit due to its close proximity to the proper ground-neutral bond in the main
panel.

Voltage Measurements

The line voltage measurement should be /-10% fluctuation at 60 Hz.  The peak volt-
age should be 1.414 times the rms line voltage reading for a clean sine waveform.  Ground-to-
neutral voltage should be less than 2 VAC.  In a single-phase circuit, a higher ground-neutral
voltage indicates excessive current leakage between the neutral and ground conductors.  In a 3-
phase circuit with a shared neutral, a high ground-neutral voltage could indicate an unbalanced
load between the three phases or harmonic distortion on the shared neutral. Excessive ground-
neutral voltage may result in inconsistent or intermittent equipment performance.  

Legend 

On
Off
Flashing

F

The Voltage Drop (

V

D

) screen dual displays percent voltage drop with a 15 amp load along

with the resultant loaded voltage (

V

L

).  This main menu has a submenu, which also dis-

plays the percent voltage drop and loaded voltage with 20 amp and 12 amp loads.  To navi-
gate through the submenu, use the side arrow button (     ).

The Amperage

(A) 

menu displays the Estimated Load on Line (

ELL

) in real-time and holds

the maximum amperage in the upper right of the display. The main menu has a submenu
positioned horizontally which displays (

ASCC1

), Available Short-Circuit Current from H-N

and (

ASCC2

) Available Short Circuit Current H-N-G. To navigate through the submenu, use

the side arrow button. (     )

The Impedance (

Z

) main menu displays the impedance in ohms (

) of the hot conductor.

This main menu has a sub-menu positioned horizontally at the bottom of the screen that
also displays the neutral (

N

) and ground (

G

) conductor impedances.  To navigate through

the submenu, use the side arrow button (

).  Note that testing the ground impedance will

trip a GFCI protected circuit. 

GFCI Test Button

Depressing this button displays the GFCI main menu.  Two tests can
be performed in this menu:  

GFCI

and 

EPD

.  The GFCI tests 

G

round

F

ault 

C

ircuit 

I

nterrupting devices by faulting 6-9mA from hot-to-

ground per UL-1436.  The 

EPD

tests those breakers, which have an

E

quipment 

P

rotective 

D

evice feature that trips the breaker if a ground fault of greater than 30mA

is detected.  Pressing the side arrow button (

) navigates between these two tests.  Once the

desired test is highlighted, depress the GFCI test button on the keypad to activate the test.

AFCI Test Button

Depressing this button displays the AFCI main menu.  Two tests 
can be performed in this menu:  

AFCI

and 

NEUT

. The AFCI 

tests 

A

rc 

F

ault 

C

ircuit 

I

nterrupting devices by creating a 106-141

amp short-duration arc between the hot and neutral conductors
per UL1436.  The 

NEUT

tests for a Shared 

Neut

ral or falsely grounded neutral conductor,

which causes AFCI breakers to nuisance trip with normal loads.  This test applies 300mA
between hot and neutral to ensure that the AFCI breaker does not trip.

Testing Procedure

Wiring Verification

Immediately after being inserted into a receptacle, the 
SureTest displays the IDEAL logo while it performs a battery 
of tests.  The first test result displayed is the wiring condition.
The SureTest checks for the following conditions and indicates
the test result on the display.

3

ND 5481-6 61-164 165 Ins  8/28/08  1:55 PM  Page 3

Summary of Contents for SureTest 61-164

Page 1: ...circuit interrupter AFCI devices to ensure that AFCI breakers protecting the circuit have been installed correctly This test dis rupts the electrical supply if a functional AFCI is present This tool...

Page 2: ...vi gate through the submenu use the side arrow button The Amperage A menu displays the Estimated Load on Line ELL in real time and holds the maximum amperage in the upper right of the display The main...

Page 3: ...e current on the branch circuit If a voltage drop reading changes significantly from one receptacle to the next then the problem is a high impedance point at or between two receptacles It is usually l...

Page 4: ...main menu The GFCI symbol in the display should be highlighted as the default test Press the side arrow button to highlight the EPD symbol Then press the GFCI button to activate the test The actual c...

Page 5: ...ed The AFCI device should trip causing the display to blank out with the loss of power If the AFCI fails to trip the SureTest will not lose power and the display shows a dimly lit GFCI Test GFCI trips...

Page 6: ...defective Replace AFCI High source of Check for line impedance high voltage or resistance drop Re wire circuit per AFCI manufacturer s Instructions Optional Accessories 61 183 Alligator Clip Adapter T...

Page 7: ...Instrument has been evaluated and complies with insulation category III overvoltage cate gory III Pollution degree 2 in accordance with IEC 644 Indoor use Measurement Specifications All specifications...

Page 8: ...product including but not limited to implied warranties of merchantability and fitness for a particular purpose are limited to the above The manufacturer shall not be liable for loss of use of the ins...

Page 9: ...ncionamiento de los equipos Los riesgos personales de descarga el ctrica se originan en conexiones a tierra incorrectas tierras falsas y o ausencia de protecci n contra fallas de tierra Los incendios...

Page 10: ...tando estas rutinas Para evitar este problema mantenga oprimido el bot n del teclado cada vez hasta que cambie el men Las mediciones tomadas por el SureTest se dividen en cinco men s principales que s...

Page 11: ...60 Hz La tensi n pico debe ser 1 414 veces la tensi n eficaz de l nea en el caso de una onda senoidal limpia La tensi n de tierra a neutro debe ser inferior a 2 VCA En un circuito monof sico una tensi...

Page 12: ...rceptible a medida que uno se acerca al primer dispositivo del circuito significa que el problema est entre el primer dispositivo y el tablero Verifique visualmente las ter minaciones del primer dispo...

Page 13: ...posibles posibles Prueba de disyuntores GFCI Para probar el dispositivo GFCI SureTest crea un desequilibrio entre los conductores vivo y neutro haciendo circular una peque a corriente de fuga del viv...

Page 14: ...ibles posibles El GFCI no GFCI El puede se dispara estar defectuoso Prueba de disyuntores AFCI S lo 61 165 El instrumento SureTest con AFCI aplica 8 a 12 pulsos de corriente en menos de medio segundo...

Page 15: ...1000 Park Ave Sycamore IL 60178 Consejos para la resoluci n de problemas Medici n Resultado Problema Causas Soluciones esperado posibles posibles AFCI defectuoso Reemplace el AFCI Accesorios opcionale...

Page 16: ...dichos da os y perjuicios gastos o p rdidas econ micas Las leyes estatales var an por lo que las limitaciones o exclusiones anteriores pueden no aplicarse en su caso Esta garant a le da derechos legal...

Page 17: ...de c blage 33 61 164 61 165 61 165 GFCI AFCI RMS True S u r e e T s t SureTest Circuit Analyzer Introduction A l aide d une technologie brevet e les analyseurs de circuits SureTest regardent travers...

Page 18: ...uton fl che lat rale L cran de Chute de tension VD affiche simultan ment le pourcentage de chute de tension avec une charge de 15 A et la tension charg e VL r sultante Ce menu a un sous menu qui affic...

Page 19: ...es possibles 37 sion terre neutre lev e pourrait signaler une charge d s quilibr e entre les trois phases ou une distorsion harmonique sur le neutre partag Une tension terre neutre excessive peut entr...

Page 20: ...p dance de terre lev e 0 003 pi de fil de 12 AWG 1 pour prot ger les personnes 40 39 Mesure de charge estim e sur la ligne ELL Le SureTest estime la charge sur un circuit de d rivation afin de fournir...

Page 21: ...entiel Directive UL pour le temps de d clenchement Remarques 1 Pour tester un GFCI dans un circuit bifilaire pas de terre il faut utiliser l adaptateur de continuit de terre N 61 175 Connecter la pinc...

Page 22: ...e disjoncteurs sur d faut d arc produisent des caract ristiques qui imitent certaines formes de production d arc De ce fait le testeur peut donner une fausse indication que l ICDA ne fonctionne par no...

Page 23: ...de l adaptateur de continuit de terre l armoire ou au ch ssis de mat riel doit assurer un chemin la terre et en cons quence un tat de c blage normal sur le SureTest Une fois l adaptateur de continuit...

Page 24: ...p cifiques et il est possible que vous b n ficiiez galement d autres droits lesquels varient d tat tat La garantie se limite exclusivement la r paration ou au remplacement il n est accord aucune garan...

Reviews: