background image

Troubleshooting Tips

Measurement

Expected

Problem

Possible

Possible

Result

Causes

Solutions

Check wiring and re- 

wire device according

to manufacturer’s

instructions.

AFCI defective.

Replace AFCI.

High source of 

Check for 

line impedance 

high voltage

or resistance. 

drop.

Re-wire circuit

per AFCI

manufacturer’s

Instructions.

Optional Accessories

#61-183 Alligator Clip Adapter

This adapter allows the SureTest to analyze non-outlet based circuits for branch circuit 
safety and performance.  Simply plug the alligator clip adapter into the IEC connection on
the front of the SureTest.  Then, properly connect the hot (black), neutral (white) and ground
(green) alligator clips onto the circuit.  Correct test results are dependent on making good
connections with the alligator clips onto the circuit.

WARNING: 

The SureTest is designed for 120/240VAC circuits only. Do not 

exceed the rating of the SureTest with this adapter.  

This adapter also allows the operator to use the SureTest (#61-165 only) to verify AFCI 
protection on non-outlet based circuits in bedrooms, such as on circuits used for lighting,
ceiling fans, and smoke detectors.  

#61-175 Ground Continuity Adapter

This adapter allows the operator to verify that a cabinet or equipment chassis has been
properly bonded to the system ground.  Plugging the SureTest into the ground continuity
adapter isolates the SureTest from the electrical ground.  If the equipment is properly
grounded, then connecting the alligator clip from the ground continuity adapter to the cabi-
net or equipment chassis should provide a pathway to ground, and consequently a normal
wiring condition on the SureTest.

After the ground continuity adapter has been connected, the SureTest can be used to mea-
sure the ground impedance of the cabinet or equipment chassis back to the panel.  See the
section on Line Impedance Measurements for test instructions for ground impedance.

This adapter can also be used to test GFCI receptacles on 2-wire circuits.  Connect the alligator
clip on the adapter to a ground, such as a metal water or gas pipe prior to testing the GFCI.

#61-176 Isolated Ground Adapter

This adapter allows the operator to verify that a receptacle is completely isolated from the
system ground that is bonded to other devices on the branch circuit.  Test the ground
impedance of the receptacle and record the ohms value. (See the section on Line
Impedance Testing for details on obtaining the ground impedance value).  Remove the
SureTest and plug it into the isolated ground adapter.  Attach the alligator clip to the center
receptacle screw or metal junction box, and re-insert the SureTest into the receptacle and
record the ohms value.

The isolated ground adapter creates a parallel pathway to ground, which results in a lower
ground impedance reading with the adapter versus with the receptacle with the isolated
ground.  If the two readings are the same, then the receptacle does not have an isolated
ground.  If the reading taken with the isolated ground adapter is lower, then the receptacle
has an isolated ground. 

Maintenance

Clean case with a damp cloth and mild detergent.  Do not use abrasives or solvents.

AFCI Test

AFCI installed

incorrectly.

Shared neutral

exists.

Shared Neutral

Test

AFCI does

not trip

AFCI does

trip.

AFCI trips

AFCI does

not trip.

12

11

ND 5481-4 61-164 165 Ins  11/21/06  1:28 PM  Page 11

Summary of Contents for SureTest 61-164

Page 1: ...d disrupts the electrical supply if a functional GFCI is present The SureTest w AFCI 61 165 also tests arc fault circuit interrupter AFCI devices to ensure that AFCI breakers protecting the circuit ha...

Page 2: ...t Circuit Interrupting devices by creating a 106 141 amp short duration arc between the hot and neutral conductors per UL1436 The NEUT tests for a Shared Neutral or falsely grounded neutral conductor...

Page 3: ...ce towards the panel should show a steady decrease in voltage drop If the voltage drop is above 5 and does not noticeably decrease as you get closer to the first device on the cir cuit then the proble...

Page 4: ...a GFCI test press the GFCI button to enter the GFCI main menu The GFCI symbol in the display should be highlighted as the default test If EPD is lit then use the side arrow to highlight the GFCI symb...

Page 5: ...user know that the AFCI test is being performed The AFCI device should trip causing the display to blank out with the loss of power If the AFCI fails to trip the SureTest will not lose power and the d...

Page 6: ...nd and consequently a normal wiring condition on the SureTest After the ground continuity adapter has been connected the SureTest can be used to mea sure the ground impedance of the cabinet or equipme...

Page 7: ...nstrument has been evaluated and complies with insulation category III overvoltage cate gory III Pollution degree 2 in accordance with IEC 644 Indoor use Measurement Specifications All specifications...

Page 8: ...oduct including but not limited to implied warranties of merchantability and fitness for a particular purpose are limited to the above The manufacturer shall not be liable for loss of use of the instr...

Reviews: