Technical Data
28
HR9Z-B2202 8/2020
Safety-Related Outputs
Additional Non-Safety-Related Outputs
Characteristic
Value
Number of relay contacts, Normally Open, instantaneous 2
Maximum short circuit current IK
1 kA
Maximum continuous current, Normally Open relay
contacts
6 A
Maximum total thermal current ∑I
th
12 A
Minimum current
10 mA
Minimum voltage
5 V
Utilization category as per UL 60947-5-1
B300 and R300
Utilization category as per IEC 60947-4-1 and IEC 60947-
5-1)
AC-1: 250 V
AC-15: 250 V
DC-1: 24 V
DC-13: 24 V
Maximum current, normally open relay contacts
AC-1: 5 A
AC-15: 3 A
DC-1: 5 A
DC-13: 3 A
External fusing
10 A, category gG
Characteristic
Value
Number of semiconductor pulsed outputs
1
Output voltage
24 VDC
Maximum current
20 mA