Functions
62
HR9Z-B2202 8/2020
Application Function 3
This application function requires the start function selector to be set to positions 1 or 5, automatic
start without startup test. Refer to Start Functions
) for details.
Synchronization:
Wiring of the inputs for two-hand control devices
Characteristic
Value/Description
Typical applications
Monitoring of two-hand control devices,
type III A as per ISO 13851
Type of outputs of sensor/device providing the input signal
for application function
Normally open, normally closed and/or changeover
outputs
S## terminals to be connected
S11-S12 and S11-S13
Signals at terminals S22 and S23 are not evaluated. Do
not connect these terminals.
Dynamization
Yes
Signal interlock monitoring
No
Synchronized terminals
Synchronization time
S12 synchronized with S13
S12 and S13 have to be activated within 0.5 s.