Functions
60
HR9Z-B2202 8/2020
Application Function 1
Wiring of the inputs for Emergency Stop
Wiring of the inputs for guards
Characteristic
Value/Description
Typical applications
Monitoring of Emergency Stop circuits as per
ISO 13850 and IEC 60204-1, stop category 0
Monitoring of guards as per ISO 14119/14120
with electrical switches
Type of outputs of sensor/device providing the input signal
for application function
Normally open, normally closed and/or changeover
outputs
S## terminals to be connected
S11-S12 and S21-S22 for sensor/device A
S11-S13 and S21-S23 for sensor/device B
Dynamization
Yes
Signal interlock monitoring
Between terminals S12 and S22
Between terminals S13 and S23
Synchronization of safety-related inputs
No