B-1909-1(0)
INSTRUCTION SHEET - HS1C Series
Solenoid Type Safety Switch
2016.08
2
Specifications and Ratings
*2 Basic insulation of 4kV impulse withstand voltage is ensured between different
contact circuits and between contact circuits and LED or solenoid in the enclosure.
When both SELV (safety extra low voltage) or PELV (protective extra low voltage)
circuits and other circuits (such as 230V AC circuits) are used for the solenoid
power and contact circuits at the same time, the SELV or PELV requirements are
not met any more.
*3 The actuator locking strength is rated at 1,500N of static load. Do not apply a load
higher than the rated value. When a higher load is expected to work on the
actuator, provide an additional system consisting of another safety switch without
lock (such as the HS5D safety switch) or a sensor to detect door opening and stop
the machine.
*4 F1max. is maximum force. The actuator’s guard-locking force Fzh is calculated in
accodance with GS-ET-19 :
Ratings approved by safety agencies
1
Type
*1 Type Nos. in [ ] are not supplied as
standard.
Contact IDEC if required.
Main Circuit : 10A, Auxiliary Circuit : 3A
IEC60204-1/ EN60204-1
CSA C22.2 No.14, GB14048 5
GS-ET-19, UL508
IEC60947-5-1, EN60947-5-1
EN ISO / ISO14119
IP67 (IEC60529)
100 mΩ maximum (Ini ial value)
20 N minimum
11 mm minimum
0.05 to 1.0 m/s
900 operations/hour
Actuator Tensile Strength
when Locked
Operating Speed
Operating Frequency
‹Ue , Ie›
(Reference Values)
Contact Ra ings
Thermal Current ‹Ith›
Applicable Directives
Applicable Standards
AC
DC
AC
DC
Standards for Use
Degree of Protection
Contact Resistance
Direct Opening Force
Direct Opening Travel
Main
Circuit
Auxiliary
Circuit
Induc ive load
(DC-13)
Resistive load
(DC-12)
Induc ive load
(AC-15)
Resistive load
(AC-12)
Induc ive load
(DC-13)
Resistive load
(DC-12)
Induc ive load
(AC-15)
Resistive load
(AC-12)
30V 125V 250V
10A 10A 6A
10A 5A 3A
6A - -
3A 0.9A -
- 3A 3A
- - 3A
3A - -
3A 0.9A -
Low Voltage Direc ive, Machinery Directive
Operating Condition
Operating Temperature
Operating Humidity
Pollution Degree
Al itude
-25 to +50°C (no freezing)
45 to 85%RH (no condensation)
3
2,000m maximum
300V (Between ground and LED, solenoid circuit : 60V)
4kV (Between ground and LED, solenoid circuit : 2.5kV)
Raed Insulation voltage ‹Ui›
Inpulse withstand voltage ‹Uimp›
Class of Protection
Class
I
( EC61140) *2
B10d
2,000,000 (EN ISO 13849-1 Annex C Table C.1)
Shock Resistance
Vibration Resistance
Operating Extremes :10 to 55Hz, half amplitude 0.5mm
Damage Limits : 30Hz, half amplitude 1.5mm
Fzh=1,500N minimum
F1max.=1,950N minimum (GS-ET-19) *3, *4
Damage Limits : 1,000m/s
2
Mechanical Durability
1,000,000 operations min. (GS-ET-19)
Electrical Durability
(900 operations / hour)
1,000,000 operations min. (AC/DC 24V 100mA)
100,000 opera ions min. (AC-12 250V•6A)
(Examples of Mounting on Hinged Doors)
(Examples of Mounting on Sliding Doors)
3
Mounting Examples
• Install the interlock switch on the immovable machine or guard, and install the
actuator on the movable door. Do not install both interlock switch and actuator on
the
movable door, otherwise he angle of insertion of the actuator to he safety switch
may become inappropriate, and failure will occur.
Hinged
Door
HS9Z-A2
Actuator
Safety
Switch
Door
Safety
Switch
HS9Z-A1
Actuator
Lock
Door Stop
Latch
HS9Z-A1
Actuator
When the center of the hinged door is on
the extension line of the contact surface
of actuator and safety switch.
When he center of the hinged door is on
the extension line of he actuator
mounting surfase.
When using the safety switch for a hinged door, the minimum radius of the applicable
door is shown in the following figures.
Minimum Radius of Hinged Door
Door Hinge
Minimum Radius
230mm
Door Hinge
Minimum Radius
130mm
Minimum Radius
400mm
Minimum Radius
240mm
Door Hinge
Door Hinge
R(Red), G(Green) (Φ12Lens)
LED lamp
10mA
24VDC
Approx. 10W
Rated Voltage × 10% minimum (at 20°C)
Rated Voltage × 85% maximum (at 20°C)
415mA
24VDC
250V AC,10A fast acting type fuse
Short-Circuit Protective Device
g
Cont ct Resistance
Conditional short circuit current 100A(250V)
Illumination Color
Light Source
Rated Current
Rated Operating Voltage
Rated Power Consumption
Turn OFF Voltage
Turn ON Voltage
Rated Current
Rated Operating Voltage
Solenoid
Indicator
CAUTION
The figures shown above are based on the condition that the actuator enters and
exits the actuator entry slot smoothry when the door is closed or opened. Since
there may be deviation or dislocation of the hinged door, make sure of correct
operation in the actual application before installation.
Door Hinge
Minimum
Radius
50mm
Door Hinge
Minimum
Radius
80mm
• L-shaped actuator : HS9Z-A2
• Adjustable actuator : HS9Z-A3
Thank you for purchasing this IDEC product. Confirm that the delivered product is
what you have ordered. Read this instruction sheet to make sure of correct operation.
In this operation instruction sheet, safety precautions are categorized in order of
importance to Warning and Caution :
Warning notices are used to emphasize that improper operation may cause severe
personal injury or death.
Caution notices are used where inattention might cause personal injury or damage to
equipment.
INSTRUCTION SHEET
Original Instructions
Solenoid Type Safety Switch
HS1C Series
S A F E T Y P R E C A U T I O N S
CAUTION
WARNING
Fzh =
maximum force (F1max.)
Safety coefficient (=1.3)
Circuit Diagram No.
Main Circuit Auxiliary Circuit
blank : 1NC+1NC 1NO/1NO
1 : 1NC+1NC 1NO
2 : 1NC+1NC 1NC+1NC
3 : 1NC
+
1NC 1NC
Solenoid voltage
4 : DC24V
LED voltage
4 : DC24V
[ 0 ] : Without LED
Solenoid unit mounting position
R : Right side
[ L ] : Left side
Housing Color
R : Red
Indicator Color
G : Green
R : Red
HS1C-R144R-R
(1) TÜV rating
AC-15 250V, 3A
(3) CCC rating
AC-15 250V, 3A
DC-13 125V, 0.9A
(2) UL, c-UL rating
3A, 250V ac, General Use
3A, 30V dc, Resistive