background image

B-2048-1(1)

INSTRUCTION SHEET - HS1T Series 

Solenoid Type Safety Switch

( 1 / 9 )

2019.07

2

Specifications and Ratings

*2  Ratings approved by safety agencies
 

(1)TÜV/CCC rating  AC-15 250V/0.75A

 

 

DC-13 30V/

1

.0A

 

(2)UL , c-UL rating  0.75A, 250V ac, Pilot Duty

 

 

1A, 30V dc, Pilot Duty

The M20 threaded opening must be filled by a Listed or 

Recognized Component Liquid-Tight Flexible Cord Fitting 

in order to maintain the Tye 4X Indoor use only rating.

*3  Basic  insulation  of  2.5kV  impuise  withstand  circuits  and  between  contact  circuit 

SELV(safety extra low voltage) or circuits (such as 230V AC circuits) at the same 

time, the SELV or PELV arequirements are met any more.

*4  The actuator locking strength is rated at 5000N of static load. Do not apply a load 

higher  than  the  rated  value.  When  a  higher  load  is  expected  to  work  on  the 

actuator, provide an additional system consisting of another safety switch without 

lock (such as the HS5D safety switch) or a sensor to detect door opening and stop 

the machine.

1

Type

HS1T-VD44ZLM-G

Solenoid Voltage / Lock Mechanism

 

4 : 24V DC / Spring Lock

  7Y : 24V DC / Solenoid Lock
Pilot Light Rated Voltage

 

4 : 24V DC

Indicator Color 

 

G : Green

Circuit Code

Rear Unlock Button

 Blank : Without Rear Unlock Button 

 

L : Rear Unlock Button

     

Head material

Z:Metal

CAUTION

Solenoid lock type

• This safety switch is designed to lock the actuator while the solenoid is energized 

and to release it when deenergized.

• When the power to the solenoid is interrupted by accident, such as disconnection, 

the lock is released before a machine stops ompletely. Then, the worker may be 

exposed to hazards. 

• This safety switch can be used only for limited applications which do not especially 

need to be locked for safety.

Applicable Standards

Applicable Directives

Thermal Current ‹ h›

Contact Ratings

(Reference Values)

‹Ue, Ie›*2

Rated Operating Voltage
Rated Current
Turn ON Voltage
Turn OFF Voltage
Rated Power Consumption
Rated Operating Voltage
Rated Current
Light Source
Illumination Color

Standards for Use

Solenoid

Indicator

Operating Condition

Inpulse withstand voltage

‹Uimp›

Raed Insulation voltage‹Ui›

Interlocking device Type

/ the level of coded

Device

Short-circuit Protective

current

Condi ional short circuit

Degree of Protection

Contact Resistance

Direct Opening Force

Direct Opening Travel

when Locked

Actuator Tensile Streng h

Electrical Durability

Mechanical durability

B10d

Operating Speed

Operating Frequency

Class of Protection

DC24V  100%  duty  cycle

200 mA (initial value)

Rated voltage x 85% maximum (at 20°C)

Rated voltage x 10% minimum (at 20°C)

Approx. 5W

DC24V 100% duty cycle

10 mA

LED

Green

Type 2 Interlocking device

/ low level coded actuator (EN ISO / ISO14119)

EN ISO / ISO14119, IEC60947-5-1, EN60947-5-1, 

GS-ET-19,UL508, CSA C22.2 No.14, GB/T 14048. 5

IEC60204-1/EN60204-1

Low Voltage Directive, Machinery Directive

2.5A

AC  Resistive load (AC12)

 

Inductive load (AC15)

DC  Resistive load (DC12)

 

Inductive load (DC13)

 30V 

125V  250V

  - 

2.5A 

1.5A

  - 

1.5A  0.75A

 2.0A 

0.4A 

0.2A

 1.0A 

0.22A  0.1A

Class

 II

 (IEC61140) *3

900 opera ions/hour

0.05 to 1.0 m/s

2,000,000 (ISO 13849-1 Annex C Table C.1)

2,000,000 operations minimum (GS-ET-19)

The Rear Unlock Button: 3000 operations

minimum (Type HS1T-

L)

100,000 operations min. (AC-15 250V/0.75A)

2,000,000 operations min. (AC/DC 24V 100mA)

(900 operations / hour)

Fzh=5,000N minimum   

F1max=6500N minimum (GS-ET-19)  *4, *5   

12 mm minimum 

120N minimum

50 mΩ maximum (initial value)

IP67 (IEC60529) , Type 4X Indoor Use Only
50A(250V)

Use 250V / 10A fast acting type fuse *6

Operating Temperature

Operating Humidity

Pollution Degree

Altitude

2.5kV (Between ground and  LED, solenoid circuit : 0.5kV)

250V (Between ground and LED, solenoid circuit : 30V) 

-25 to +55°C (no freezing)

20 to 95%RH (no condensation)

3 (Inside 2)

2000m maximum

Thank  you  for  purchasing  this  IDEC  product.  Confirm  that  the  delivered  product  is 

what you have ordered. Read  his instruction sheet to make sure of correct operation.

In this operation instruction sheet, safety precautions are categorized in order of 

importance to Warning and Caution :

Warning notices are used to emphasize that improper operation may cause severe 

personal injury or death.

Caution notices are used where inattention might cause personal injury or damage to 

equipment.

INSTRUCTION SHEET

Original Instructions

Solenoid Type Safety Switch

HS1T Series

S A F E T Y   P R E C A U T I O N S

CAUTION

WARNING

Shock Resistance

Vibration Resistance

Operating Extremes: 100m/s

2

, Damage Limits: 1000m/s

2

Operating Extremes:10 to 55 Hz, half amplitude 0.35mm 

Damage Limits: 30 Hz, half amplitude 1.5mm

Conduit Cover

 

M : Standard type (M20)

  SM : Cable side-routed type (M20)

Standard type

Contact Congifiguration

*1  Only type No. on √ mark are supplied 

      as standard.

 

Contact IDEC for the other if required.

Spring Lock Type Solenoid Lock Type

Main

circuit

-

-

-

-

-

-

-

-

-

-

-

-

-

-

1NC+1NC

1NC+1NC

-

-

1NC+1NC

1NC+1NC

1NC+1NC

1NC+1NC

1NC+1NC

1NC+1NC

1NC+1NC

1NC+1NC

-

-

-

-

-

-

-

-

HS1T-

7Y4ZM-G

-

-

-

-

-

-

-

-
-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

HS1T-

44ZLM-G

-

-

-

-

-

-

-

-

-

-

-
-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

HS1T-

44ZM-G

-

-

-

-

-


-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

Door monitor

circuit 

1NC

2NC

1NC,1NO

-

1NC,1NO

1NC,1NO

2NC

2NC

3NC

2NC,1NO

1NC

1NC

1NO

1NO

-

1NO

-

1NO

1NO

1NC

1NC

2NC

1NC,1NO

-

-

1NO

1NO

1NC

1NC

2NC

1NC,1NO

-

-

Lock monitor

circuit 

1NC

-

-

2NC

1NC,1NO

2NC

1NC,1NO

2NC

1NC

1NC

3NC

2NC,1NO

3NC

2NC,1NO

-

1NC

1NC,1NO

1NO

1NC

1NO

1NC

-

-

2NC

1NC,1NO

1NC,1NO

2NC

1NC,1NO

2NC

1NC

1NC

3NC

2NC,1NO

XD 

XF 

XG 

XH 

VA 

VB 

VC 

VD 

VF 

VG 

VH 

  VJ  

VW 

VX 

DD 

XB 

XJ 

TA 

TB 

TC 

TD 

TF 

TG 

TH 

TJ 

Rear Unlock Button

Weight

Approx. 450g

Thermal Current‹lth›

Summary of Contents for HS1T Series

Page 1: ...cle 10 mA LED Green Type 2 Interlocking device low level coded actuator EN ISO ISO14119 EN ISO ISO14119 IEC60947 5 1 EN60947 5 1 GS ET 19 UL508 CSA C22 2 No 14 GB T 14048 5 IEC60204 1 EN60204 1 Low Voltage Directive Machinery Directive 2 5A AC Resistive load AC12 Inductive load AC15 DC Resistive load DC12 Inductive load DC13 30V 125V 250V 2 5A 1 5A 1 5A 0 75A 2 0A 0 4A 0 2A 1 0A 0 22A 0 1A Class I...

Page 2: ...ctual applica ion before installation Actuator Mounting Reference Position As shown below the mounting reference position of the actuator inserted into the safety switch is After mounting the actuator remove the actuator stop from the safety switch When using the safety switch for a hinged door the minimum radius of the applicable door is shown in the following figures Minimum Radius of Hinged Doo...

Page 3: ... cycling testing of the device to the control system to prevent product failure Regardless of door types do not use the safety switch as a door stop Install a mechanical door stop to the end of the door to protect the safety switch against excessive force Mount the actuator so that it will not hit the operator when the door is open other wise injury may be caused Pay attention to the management of...

Page 4: ... safety hedge Use the rear unlock indicator by attaching it to the display area on either side of the safety switch The Rear Unlock Button Lock Release Rear Unlock Status Normal Status Contact Configuration and Operation Contact Congifiguration 11 9 HS1T TJ HS1T TG HS1T TF HS1T TD HS1T TC HS1T TB HS1T TA HS1T J HS1T G HS1T F HS1T D HS1T C HS1T B HS1T A HS1T XB HS1T DD HS1T VG HS1T VH HS1T VF HS1T ...

Page 5: ...ng for guard locking devices Section 5 7 2 2 When a lock monitor circuit contact has the locking monitoring marking it means that one circuit contact can monitor the position and the locking function of the protective door The locking monitoring circuit contact turns ON only when the protective door is closed and locked note Both types of HS1T safety switches spring lock type switches and solenoid...

Page 6: ...of gasket is completely tightening the cable The waterproof gasket is not properly tightening the cable Spring Force Terminal Spring Force Terminal Safety Switch A Gasket Sheath B Terminal Cover CAUTION Make sure not to lose any screw when removing the terminal cover from the switch Please make sure the cable is insterted deep enough into the terminal cover so that the waterproof gasket can tighte...

Page 7: ...d by IDEC CORPORATION HS9Z A11T Actuator HS1T VB4 Safety Switch with Solenoid Used as open close monitor of guard Guard Open Output Circuit HR1S AF Safety relay module One of the example of the circuit Safety relay module HR1S AF series manufactured by IDEC CORPORATION HS9Z A11T Actuator HS1T VB4 Safety Switch with Solenoid Used as open close monitor of guard Guard Open Example of a circuit diagra...

Page 8: ...ator Rear Unlock Button Rear Unlock Button RP RP 7 8 30 125 5 Main body moun ing hole layout HS9Z A12T Actuator HS9Z A11T Actuator Slot Plug 取付基準 Actuator center position 30 40 143 97 8 40 1 56 2 59 4 9 20 8 30 40 20 6 5 61 6 2 5 17 8 35 56 8 4 7 1 22 54 9 52 3 19 1 0 5 11 5 16 6 0 5 7 1 5 1 0 5 2 6 0 5 8 4 6 4 φ 5 2 φ 5 1 φ 5 1 7 8 30 97 8 HS9Z A11T Actuator HS9Z A12T Actuator HS9Z A11T Actuator ...

Page 9: ... its validity Applicable EU Directive Low Voltage Directive 2014 35 EU Machinery Directive 2006 42 EC RoHS Directive 2011 65 EU Applicable Standard s EN 60947 5 1 GS ET 19 EN 50581 20 5 11 5 22 40 40 42 5 12 3 0 8 43 18 6 3 5 1 φ 5 1 φ 15 90 22 40 22 43 18 6 47 9 19 3 0 8 φ 5 1 φ 15 When installed on 3 5 1 Actuator Stop Supplied with actuator When installed on Actuator dimensions Type HS9Z A11T To...

Reviews: