System Manual HS3A-H21M4
14
Requirements for connection cables
Caution!
Risk of damage to device or malfunctions as a result of incorrect connection
cables.
Use connection components and connection cables from IDEC
On the usage of other connection components, the requirements in the fol-
lowing table apply. IDEC provides no warranty for safe function in case of
failure to comply with these requirements.
Observe the following requirements for the connection cables:
Parameter
Value
Unit
Conductor cross-section min.
0.34
mm
2
R max.
60
Ω
/km
C max.
120
nF/km
L max.
0.65
mH/km
Recommend cable type
LIYY 8x or 5x (for series connection)
0.34mm
2
Table 1