2: D
EVICES
2-4
FC6A S
ERIES
MICROS
MART
L
ADDER
P
ROGRAMMING
M
ANUAL
FC9Y-B1726
Special Internal Relay
Special Internal Relay Device Addresses
Note:
R/W is an abbreviation for read/write.
The notation for the R/W field is as follows.
R/W: The device can be both read from and written to
R: Read-only
W: Write-only
Do not write to data in the area marked as reserved in the special internal relays list. Otherwise the system may not operate
correctly.
Warning
Device
Address
Description
When
Stopped
Power
OFF
R/W
M8000
Start Control
Maintained
Maintained
R/W
M8001
1-s Clock Reset
Cleared
Cleared
R/W
M8002
All Outputs OFF
Cleared
Cleared
R/W
M8003
Carry (Cy) or Borrow (Bw)
Cleared
Cleared
R/W
M8004
User Program Execution Error
Cleared
Cleared
R/W
M8005
Communication Error
Maintained
Cleared
R/W
M8006
Communication Prohibited Flag (When Data Link Master)
Maintained
Maintained
R/W
M8007
Initialization Flag (When Data Link Master)/Stop Communication Flag (When
Data Link Slave)
Cleared
Cleared
R/W
M8010
Status LED Operation
Operating
Cleared
R/W
M8011
M8012
— Reserved —
—
—
—
M8013
Calendar/Clock Data Write/Adjust Error Flag
Operating
Cleared
R/W
M8014
Calendar/Clock Data Read Error Flag
Operating
Cleared
R/W
M8015
— Reserved —
—
—
—
M8016
Calendar Data Write Flag
Operating
Cleared
R/W
M8017
Clock Data Write Flag
Operating
Cleared
R/W
M8020
Calendar/Clock Data Write Flag
Operating
Cleared
R/W
M8021
Clock Data Adjust Flag
Operating
Cleared
R/W
M8022
User Communication Receive Instruction Cancel Flag (Port 1)
Cleared
Cleared
R/W
M8023
User Communication Receive Instruction Cancel Flag (Port 2)
Cleared
Cleared
R/W
M8024
BMOV/WSFT Executing Flag
Maintained
Maintained
R/W
M8025
Maintain Outputs While Stopped
Maintained
Cleared
R/W
M8026
User Communication Receive Instruction Cancel Flag (Port 3)
Cleared
Cleared
R/W
M8027
High-speed Counter (Group 1/I0)
Count Direction Flag
Maintained
Cleared
R/W
M8030
Comparison Output Reset
Cleared
Cleared
R/W
M8031
Gate Input
Maintained
Cleared
R/W
M8032
Reset Input
Maintained
Cleared
R/W
M8033
User Communication Receive Instruction Cancel Flag (Port 4)
Cleared
Cleared
R/W
M8034
High-speed Counter (Group 3/I3)
Comparison Output Reset
Cleared
Cleared
R/W
M8035
Gate Input
Maintained
Cleared
R/W
M8036
Reset Input
Maintained
Cleared
R/W
M8037
— Reserved —
—
—
—
M8040
High-speed Counter (Group 4/I4)
Comparison Output Reset
Cleared
Cleared
R/W
M8041
Gate Input
Maintained
Cleared
R/W
M8042
Reset Input
Maintained
Cleared
R/W
M8043
High-speed Counter (Group 5/I6)
Count Direction Flag
Maintained
Cleared
R/W
M8044
Comparison Output Reset
Cleared
Cleared
R/W
M8045
Gate Input
Maintained
Cleared
R/W
M8046
Reset Input
Maintained
Cleared
R/W
M8047
M8050
— Reserved —
—
—
—
Summary of Contents for MICROSmart FC6A Series
Page 1: ...B 1726 7 FC6A SERIES Ladder Programming Manual ...
Page 8: ...Preface 7 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 32: ...1 OPERATION BASICS 1 20 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 96: ...3 INSTRUCTIONS REFERENCE 3 18 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 130: ...4 BASIC INSTRUCTIONS 4 34 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 192: ...9 SHIFT ROTATE INSTRUCTIONS 9 12 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 272: ...12 DISPLAY INSTRUCTIONS 12 24 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 284: ...14 REFRESH INSTRUCTIONS 14 6 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 502: ...25 DATA LOG INSTRUCTIONS 25 22 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 546: ...26 SCRIPT 26 44 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 598: ...APPENDIX A 14 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...