2: D
EVICES
2-10
FC6A S
ERIES
MICROS
MART
L
ADDER
P
ROGRAMMING
M
ANUAL
FC9Y-B1726
■
M8013: Calendar/Clock Data Write/Adjust Error Flag
When the clock writing or clock adjustment processing could not be executed normally, M8013 is turned on. It is turned off
when the processing completes normally.
■
M8014: Calendar/Clock Data Read Error Flag
When an error occurs while calendar/clock data is read from the internal clock to the special data registers (D8008 to D8021),
M8014 is turned on. It is turned off when reading completes normally.
■
M8016: Calendar Data Write Flag
When M8016 is turned on after writing data to the calendar data (write-only) special data registers (D8015 to D8018), the
calendar data (year, month, day, day of the week) is written to the internal clock.
■
M8017: Clock Data Write Flag
When M8017 is turned on after writing data to the clock data (write-only) special data registers (D8019 to D8021), the clock
data (hours, minutes, seconds) is written to the internal clock.
■
M8020: Calendar/Clock Data Write Flag
When M8020 is turned on after writing data to the calendar/clock data (write-only) special data registers (D8015 to D8021), the
calendar data (year, month, day, day of the week) and the clock data (hours, minutes, seconds) is written to the internal clock.
■
M8021: Clock Data Adjust Flag
When M8021 is turned on, the clock is adjusted with respect to seconds.
•
When M8021 is turned on, if the seconds are between 0 and 29, the seconds will be set to 0 and the minutes remain the
same.
•
When M8021 is turned on, if the seconds are between 30 and 59, the seconds will be set to 0 and 1 will be added to the
minutes.
■
M8022: User Communication Receive Instruction Cancel Flag (Port 1)
While M8022 is on, user communication (receive instruction) executing on Port 1 is canceled.
■
M8023: User Communication Receive Instruction Cancel Flag (Port 2)
While M8023 is on, user communication (receive instruction) executing on Port 2 is canceled.
■
M8024: BMOV/WSFT Executing Flag
While the WSFT (word shift) instruction or the BMOV (block move) instruction is executing, M8024 is turned on. When
completed, M8024 is turned off.
■
M8025: Maintain Outputs While Stopped
When the FC6A Series MICROSmart is stopped while running with M8025 turned on, the outputs maintain their runtime status.
When set to run again, M8025 is automatically turned off.
■
M8026: User Communication Receive Instruction Cancel Flag (Port 3)
While M8026 is on, user communication (receive instruction) executing on Port 3 is canceled.
■
M8033, M8145 to M8147, M8170, M8176, M8365 to M8394: User Communication Receive Instruction Cancel
Flag (Port 4 to 33)
While these flags are on, user communication (receive instruction) being executed on the corresponding port is canceled.
M8033 = User Communication Receive Instruction Cancel Flag (Port 4)
M8145 = User Communication Receive Instruction Cancel Flag (Port 5)
M8146 = User Communication Receive Instruction Cancel Flag (Port 6)
M8147 = User Communication Receive Instruction Cancel Flag (Port 7)
M8170 = User Communication Receive Instruction Cancel Flag (Port 8)
M8176 = User Communication Receive Instruction Cancel Flag (Port 9)
M8365 = User Communication Receive Instruction Cancel Flag (Port 10)
M8366 = User Communication Receive Instruction Cancel Flag (Port 11)
M8367 = User Communication Receive Instruction Cancel Flag (Port 12)
M8370 = User Communication Receive Instruction Cancel Flag (Port 13)
M8371 = User Communication Receive Instruction Cancel Flag (Port 14)
M8372 = User Communication Receive Instruction Cancel Flag (Port 15)
M8373 = User Communication Receive Instruction Cancel Flag (Port 16)
M8374 = User Communication Receive Instruction Cancel Flag (Port 17)
M8375 = User Communication Receive Instruction Cancel Flag (Port 18)
M8376 = User Communication Receive Instruction Cancel Flag (Port 19)
M8377 = User Communication Receive Instruction Cancel Flag (Port 20)
Summary of Contents for MICROSmart FC6A Series
Page 1: ...B 1726 7 FC6A SERIES Ladder Programming Manual ...
Page 8: ...Preface 7 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 32: ...1 OPERATION BASICS 1 20 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 96: ...3 INSTRUCTIONS REFERENCE 3 18 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 130: ...4 BASIC INSTRUCTIONS 4 34 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 192: ...9 SHIFT ROTATE INSTRUCTIONS 9 12 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 272: ...12 DISPLAY INSTRUCTIONS 12 24 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 284: ...14 REFRESH INSTRUCTIONS 14 6 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 502: ...25 DATA LOG INSTRUCTIONS 25 22 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 546: ...26 SCRIPT 26 44 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Page 598: ...APPENDIX A 14 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...