background image

11

PS5R-V Switching Power Supplies

Installing the Panel Mounting Bracket

Latch

Latch

LOCK

LOCK

Panel Mounting Bracket (PS9Z-5R1

)

Panel Mounting Bracket (PS9Z-5R2B)

Power
Supply

Power
Supply

Tab

Tab

Slot

<Installing PS9Z-5R1

 Panel Mounting Bracket>

<Installing PS9Z-5R2B Panel Mounting Bracket>

LOCK

UNLOCK

LOCK

UNLOCK

 Push in the latch to LOCK

position.

 Install the tab on the panel 

mounting bracket into the 

slot on the power supply.

 Install the brackets as 

shown on the left.

 Ensure that the panel 

mounting bracket is locked 

by the latch.

 Pull out the latch to

UNLOCK position.

 

Insert the tab on the panel 

mounting bracket into the 

slot on the power supply.

 

Push in the latch to LOCK 

position.

 

Ensure that the panel 

mounting bracket is locked 

by the latch.

Installing PS9Z-6R2F Side-mount Panel 

Mounting Bracket

Install the bracket on the switching power supply using four 

M3 × 6 countersunk screws supplied with the bracket.

Adjustment of Output Voltage

The output voltage can be adjusted within ±10% of the rated 

output voltage (PS5R-VE: ±5%) by using the VR.ADJ control 

on the front. Turning the VR.ADJ clockwise increases the out-

put voltage. Turning the VR.ADJ counterclockwise decreases 

the output voltage.

Overcurrent Protection

The output voltage drops automatically when an overcurrent 

flows due to an overload or short circuit. Normal voltage is 

auto matically restored when the load returns to normal condi-

tions.

Insulation/Dielectric Test

When performing an insulation/dielectric test, short-circuit the 

input (between L and N) and output (bV and –V). Do 

not apply or interrupt the voltage quickly, otherwise surge volt-

ages may be generated and the PS5R-V may be damaged.

Notes for Operation

• Output interruption may indicate blown fuses. Contact IDEC.
• The PS5R-V switching power supply contains an internal fuse 

for AC input. When using with DC input, install an exter nal 

fuse for DC input. To avoid blown fuses, select a fuse in con-

sideration of the rated current of the internal fuse.

Rated Current of Internal Fuses

Part No.

Internal Fuse 

Rated Current

PS5R-VB/VC

2A

PS5R-VD/VE/VF

4A

PS5R-VG

6.3A

• Avoid overload and short-circuit for a long period of time, 

oth erwise the internal elements may be damaged.

• DC input operation is not subject to safety standards.

Rust and Scratches on Metal parts

Hot-dip galvanized steel and bonderized steel are used for the 

PS5R-V. Rust on the edge and scratches on the surfaces may 

be developed depending on the storage condition, but the 

performance of the PS5R-V is not affected.

Noise

Small acoustic noise inside the PS5R-V may be heard de-

pending on the input voltage and load, but the performance of 

the PS5R-V is not affected.

Operating Instructions

Summary of Contents for PS5R-V Series

Page 1: ...PS5R V Switching Power Supplies ...

Page 2: ...1 Improved reliability Reduces installation space inside the panel Reduced wiring flexible installation Suitable for global and semiconductor applications Spring up terminals accepts wiring of ring terminals No need to worry about loosing screws Six mounting directions Compliant with International Safety Standards Meets SEMI F47 Sag Immunity 208V AC input Voltage sag ride through capabilities for ...

Page 3: ...R VB VC VD VE only 2 EN60950 1 EN50178 only PS5R V Package Quantity 1 Output Capacity Part No Input Voltage Output Voltage Output Current 10W PS5R VB05 100 to 240V AC Voltage range 85 to 264V AC 100 to 370V DC 5V 2 0A 15W PS5R VB12 12V 1 3A PS5R VB24 24V 0 65A 30W PS5R VC12 12V 2 5A PS5R VC24 24V 1 3A 60W PS5R VD24 24V 2 5A 90W PS5R VE24 24V 3 75A 120W PS5R VF24 24V 5 0A 240W PS5R VG24 24V 10 0A D...

Page 4: ...1 min auto reset 105 min auto reset Operation Indicator LED green Dielectric Strength Between input and output terminals 3 000V AC 1 minute Between input and ground terminals 2 000V AC 1 minute Between output and ground terminal 500V AC 1 minute Insulation Resistance Between input and output terminals 100MΩ min 500V DC megger Between input and ground terminal 100MΩ min 500V DC megger Operating Tem...

Page 5: ...ter Overcurrent Detection PS5R VE24 L N INPUT V ADJ V V Switching Control Detection Fuse Rectifying Active Filter Ripple Filter Rectifying Line filter Overcurrent Detection PS5R VF24 L N INPUT V ADJ V V Switching Control Detection Fuse Rectifying Rectifying Active Filter Ripple Filter Line filter Overcurrent Detection PS5R VG24 L N INPUT V ADJ V V Switching Control Detection Fuse Rectifying Active...

Page 6: ...t Current Output Current Output Current Output Current Output Current Mounting F Mounting C E 30 20 10 0 10 20 30 40 50 60 70 80 0 10 20 30 40 50 60 70 80 90 100 Mounting B D Mounting A Operating Temperature C Output Current 30 20 10 0 10 20 30 40 50 60 70 80 0 10 20 30 40 50 60 70 80 90 100 30 20 10 0 10 20 30 40 50 60 70 80 0 10 20 30 40 50 60 70 80 90 100 Operating Temperature Approved by Safet...

Page 7: ...t terminal V Negative output terminal VR ADJ Output Voltage Adjustment Turning clockwise increases the output voltage Turning counterclockwise decreases the output voltage DC ON Operation Indicator green Lights when the output voltage is on Overcurrent Protection Characteristics 30 0 100 0 100 0 0 100 95 0 0 100 95 100 100 105 and over 105 and over 101 and over Output Current Output Current Output...

Page 8: ...125 3 8 115 98 8 5 46 23 11 5 11 5 4 5 44 9 35 3 3 8 121 36 95 79 8 20 10 10 108 3 8 4 5 24 9 35 3 3 8 95 4 4 35 3 27 3 61 6 12 2 8 2 90 9 5 22 5 5 M3 5 Screw Terminal 5 M3 5 Screw Terminal 5 M3 5 Screw Terminal 5 M3 5 Screw Terminal PS5R VD VE PS5R VF PS5R VG PS5R VB VC All dimensions in mm Tolerance 1mm ...

Page 9: ...e View Front View Side View Side View Back View Mounting Screws 4 M3 6 countersunk screws 13 6 16 4 96 7 5 5 28 8 10 0 10 0 12 112 102 26 105 10 2 9 9 109 8 12 24 7 112 120 102 0 110 44 62 9 26 38 105 115 36 48 125 135 36 125 10 2 9 9 122 8 135 145 28 39 28 135 28 10 5 10 5 145 10 130 6 56 138 6 56 148 6 138 6 56 70 62 3 29 5 11 8 31 11 8 2 M4 or ø2 4 5 holes 2 M4 or ø2 4 5 holes 2 M4 or ø2 4 5 ho...

Page 10: ...e used to comply with UL508 CSA C22 2 No 107 1 Applicable crimp terminal reference 7 0 max 4 1 max 5 6 min PS5R VG 6 3 min ø3 6 min Recommended tightening torque of the input and output ter minals is 1 0 to 1 3 N m 0 8 N m for UL Safety Precautions Operating Instructions Mount the PS5R V in an enclosure Do not use the PS5R V alone as an Electric Facilities for General Use Use the PS5R V for electr...

Page 11: ...ops automatically when an overcurrent flows due to an overload or short circuit Normal voltage is auto matically restored when the load returns to normal condi tions Insulation Dielectric Test When performing an insulation dielectric test short circuit the input between L and N and output between V and V Do not apply or interrupt the voltage quickly otherwise surge volt ages may be generated and t...

Page 12: ...nditions The maximum value of output capacity is within the range shown in Operating Temperature vs Output Current on page 5 1 Average operating temperature ambient temperature of switching power supply is 40 C maximum 2 The load is 80 maximum 3 Input voltage is the rated input voltage 4 Standard mounting style IDEC shall not be liable for other damages including conse quential contingent or incid...

Reviews: