3.9.2 Muting stop condition
Muting function will stop when any one of the condition below is fulfilled:
a)
One of the muting inputs switches to OFF-state.
b)
When the predefined (preset) maximum muting time T2 exceeds (1 minute and above) (Figure 3-20).
c)
Objects are detected in the protection zone which is not covered by the muting zone.
d)
Error is detected by the self-diagnostics function.
e)
During muting state
when the area is switched to other area.
Figure 3-20 shows the muting sequence.
Maximum muting period (T2)
Maximum muting period can be selected from one of these values
▶
1 minute
▶
6 minutes
▶
12 minutes
▶
Unlimited
When using the muting function in dual protection mode, Muting 3 and Muting 4 are configured in the
similar way. Same applies for muting input sequence, time interval between inputs and maximum muting
period.
Figure 3-20 Muting sequence
Summary of Contents for SE2L-H05LPC
Page 1: ...SE9Z B1865 SE2L Series Safety Laser Scanner User s Manual...
Page 100: ...SE2L User s Manual SE9Z B1865 99 Figure 7 31 b Function Figure7 31 c Area...
Page 143: ...SE2L User s Manual SE9Z B1865 142 13 External dimension 13 1 SE2L H05LP mm...
Page 144: ...SE2L User s Manual SE9Z B1865 143 13 2 SE2L H05LPC mm...
Page 145: ...SE2L User s Manual SE9Z B1865 144 13 3 Base mounting bracket mm...
Page 146: ...SE2L User s Manual SE9Z B1865 145 13 4 Rear mounting bracket mm...
Page 147: ...SE2L User s Manual SE9Z B1865 146 13 5 Simple base mounting bracket mm...
Page 149: ...SE2L User s Manual SE9Z B1865 148 13 7 Simple rear mounting bracket Long type mm...
Page 150: ...SE2L User s Manual SE9Z B1865 149 13 8 Cover Protection Bracket mm...