WindO/I-NV4 User’s Manual
13-29
3 Alarm Log Settings Dialog Box
13
Ala
rm
L
og
F
un
ctio
n
●
Options
Tab
The
Options
tab is used to configure whether or not the MICRO/I’s internal buzzer operates and the screen flashing.
■
Trigger Buzzer when Alarm occurs
Select this check box to sound a beep when an alarm has occurred.
■
Screen flashing when Alarm occurs
Select this check box to have the screen flash when an alarm occurs.
■
Buzzer and Screen Flashing
This item selects the condition for the alarm to sound the buzzer or to flash the screen. This item can only be
configured when the
Buzzer when Alarm occurs
or the
Screen flashing when Alarms occurs
is selected.
■
Stop the Sound of the Buzzer and Screen flashing
Select the check box for the items that will trigger the sound of the buzzer and screen flashing to stop.
*1 The first alarm that has occurred in a state where no alarms are active
All Alarms:
The buzzer is triggered and the screen flashing each time an alarm occur.
Alarms with the specified Level or upper: Specifies the level (2 to 8). Each time alarm with the specified level or
upper sets off, the buzzer gets triggered and screen starts flashing.
Only First Alarm:
The buzzer is triggered and the screen flashing only when the first alarm
occurs.
No beeps will sound and no screen will flash when another alarm is
already active.
When touch everywhere on the screen:
The sound of the buzzer and screen flashing stops when you touch
anywhere on the screen.
When press CHECK or All Chk. button:
The sound of the buzzer and screen flashing stops when you touch the key
buttons
CHECK
or
All Chk
. on the Alarm Log Display.
When all Alarms are recovered:
The sound of the buzzer and screen flashing stops when all the alarms are
recovered from.
Summary of Contents for WindO/I-NV4
Page 1: ...B 1701 16 User s Manual...
Page 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Page 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Page 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Page 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Page 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Page 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Page 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Page 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Page 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Page 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Page 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Page 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Page 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Page 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Page 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Page 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...