WindO/I-NV4 User’s Manual
14-9
2 Data Log Function Configuration Procedure
14
Da
ta
L
og
F
un
ctio
n
4
On the
General
tab, under
Log function
, select
Enable
.
The channel number selected on the
Data Log Settings
dialog box is displayed in
Channel No
.
5
Enter the name of the channel in
Channel Name
.
6
Under
Condition of Writing to Data Storage Area
, select the condition that will be used to write the values of the
sampled device addresses to the data storage area.
■
Fixed Period
Writes the value of source device address at a fixed interval. If
Fixed Period
is selected, specify
Time
in seconds.
■
Event Bit
Writes the value of source device address each time the monitored bit device or the bit number of the word device
changes from 0 to 1. If
Event Bit
is selected, specify the device address to monitor as the condition for writing data
in
Device Address
.
Click to display the Tag Editor. For the device address configuration procedure, refer to Chapter 2 “5.1 Device
Address Settings” on page 2-70.
■
Event Word
Writes the value of source device address each time the value of monitored word device changes. If
Event Word
is
selected, select the data size for the word device to monitor in
Data Size
, and specify the device address to monitor
as the condition for Writing data in
Device Address
.
Click to display the Tag Editor. For the device address configuration procedure, refer to Chapter 2 “5.1 Device
Summary of Contents for WindO/I-NV4
Page 1: ...B 1701 16 User s Manual...
Page 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Page 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Page 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Page 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Page 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Page 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Page 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Page 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Page 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Page 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Page 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Page 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Page 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Page 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Page 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Page 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...