3 Data Log Settings Dialog Box
14-14
WindO/I-NV4 User’s Manual
■
Edit
Registers or changes the settings for the selected channel number.
Select a channel number and click this button to display the
Individual Settings
dialog box. The settings for the
selected channel are reflected in the
Individual Settings
dialog box.
For details, refer to “3.2 Individual Settings Dialog Box” on page 14-15.
■
Up
Shifts the selected settings upward in the list.
■
Down
Shifts the selected settings downward in the list.
■
Clear All Log Data
Select this check box to erase the all log data saved in the data storage area.
■
Number of Stored Data for Data Log per Device Address
Shows the maximum amount of data storage per device address for Data Log data saved in the data storage area. If
data is saved up the maximum amount and then the maximum is exceeded, the old data is deleted and the new data
is saved.
The default is 1024.
Click to display the
Data Storage Area Management
dialog box where you can change the allocation of data
storage area memory. For details, refer to Chapter 16 “Data Storage Area” on page 16-1.
■
Sampling Method
Sets the method that will be used by the MICRO/I to read the values of device addresses.
Monitor:
Shows the write destination device address when monitor count of writings to Data Storage
Area. Shows
No
when not monitoring. Double clicking the cell displays the
Individual Settings
dialog box where you can edit the settings. For details, refer to “3.2 Individual Settings Dialog
Box” on page 14-15. This option can only be set when
Enable
is selected in
Log Function
.
Batch:
Shows the trigger device address that triggers batch output when batch outputting all the data
saved in the data storage area to the external memory device. Shows
No
when there is no batch
output. Double clicking the cell displays the
Individual Settings
dialog box where you can edit
the settings. For details, refer to “3.2 Individual Settings Dialog Box” on page 14-15.
Real Time:
Shows whether or not to perform real time output. Double clicking the cell switches between
Yes
and
No
. Data is output to the external memory device in 3 minute intervals for
Yes
channels. This option can only be set when
Enable
is selected in
Log Function
.
Words:
Shows the total number of words of the device addresses that will be sampled by the channel.
Double clicking the cell displays the
Individual Settings
dialog box where you can edit the
settings. For details, refer to “3.2 Individual Settings Dialog Box” on page 14-15. This option can
only be set when
Enable
is selected in
Log Function
.
(Trigger Device Address): Specifies the bit device or the bit number of the word device that triggers the erasure of
the data. The data for all channels is erased when the value of the configured device
address changes from 0 to 1. For the device address configuration procedure, refer to
Chapter 2 “5.1 Device Address Settings” on page 2-70.
Always: The values of the device addresses set for the data of each channel are always read. When the condition of
writing to the data storage area is satisfied, the values that were read at that point in time are written to
the data storage area.
While satisfying the condition of writing to data storage area:
The values of the device addresses set for the data of each channel are read when the condition of writing
to the data storage area is satisfied, and those values are written to the data storage area.
The total number of words of data that can be registered to the data log settings will depend on
Sampling
Method
.
• If
Sampling Method
is
Always
, the total number of words in all channels is 128 words or less.
• If
Sampling Method
is
While satisfying the condition of writing to data storage area
, the total
number of words per channel is 128 words or less.
Summary of Contents for WindO/I-NV4
Page 1: ...B 1701 16 User s Manual...
Page 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Page 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Page 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Page 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Page 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Page 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Page 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Page 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Page 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Page 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Page 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Page 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Page 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Page 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Page 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Page 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...