3 Data Log Settings Dialog Box
14-16
WindO/I-NV4 User’s Manual
■
Condition of Writing to Data Storage Area
Sets the condition to write to the sampled address values to the data storage area.
■
Monitor Count of Writings to Data Storage Area
Select this check box to monitor count of writings to Data Storage Area. The count of writings to Data Storage Area is
written to the specified device address.
■
Monitor % Space Used in Data Storage Area
Select this check box to monitor the usage of the allocated data storage area as the save destination for Data Log
data. The usage is calculated from the data storage amount allocated to the data storage area and the amount of
saved data, and then written to the specified device address.
Usage = Current amount of Data Log data ÷ Data Log data storage amount per device address (omits values after the
decimal point)
Fixed Period: Writes the value of source device address at a fixed interval. If
Fixed Period
is selected, specify
Time
in seconds.
Time:
Specifies the time in seconds (1 to 9999).
This option can only be set when
Fixed Period
is selected.
Event Bit:
Writes the value of source device address each time the monitored bit device or the bit number of the
word device changes from 0 to 1.
Event Word: Writes the value of source device address each time the value of monitored word device changes.
Data Size:
Selects the data size of the monitored device address as
16-bit
or
32-bit
.
This option can only be set when
Event Word
is selected.
Device Address: Specifies the device address to monitor as the condition for Writing data.
For the device address configuration procedure, refer to Chapter 2 “5.1 Device
Address Settings” on page 2-70.
This option can only be set when
Event Bit
or
Event Word
is selected.
If this setting is different from other channels, it cannot be displayed in the Line Chart.
(Destination Device Address): Specifies the destination word device.
For the device address configuration procedure, refer to Chapter 2 “5.1 Device Address
Settings” on page 2-70.
Report when Count of Writings to Data Storage Area has reached or exceeded
Threshold:
Writes 1 in the Report Device Address when the current
count of writings to Data Storage Area reaches or exceeds
the set threshold.
Threshold:
Specifies the count of writings to Data Storage Area that is
the basis for reporting (1 to 65535).
Report Device Address: Specifies the destination bit device or the bit number of the
destination word device.
For the device address configuration procedure, refer to
Chapter 2 “5.1 Device Address Settings” on page 2-70.
(Destination Device Address): Specifies the destination word device to write the current usage of the amount of Data Log
data storage.
For the device address configuration procedure, refer to Chapter 2 “5.1 Device Address
Settings” on page 2-70.
Report when % Space Used has reached or exceeded Threshold:
Writes 1 in the Report Device Address when the current usage
reaches or exceeds the set threshold.
Threshold:
Specifies the usage (1 to 100) that is the basis for reporting.
Report Device Address: Specifies the destination bit device or the bit number of the
destination word device.
For the device address configuration procedure, refer to
Summary of Contents for WindO/I-NV4
Page 1: ...B 1701 16 User s Manual...
Page 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Page 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Page 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Page 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Page 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Page 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Page 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Page 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Page 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Page 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Page 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Page 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Page 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Page 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Page 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Page 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...