WindO/I-NV4 User’s Manual
14-45
4 Using the Data
14
Da
ta
L
og
F
un
ctio
n
4.4 Saving the Data as a CSV File
●
Saving the Data as a CSV File
The Data Log data can be saved to the external memory device
as a CSV file or uploaded to a computer.
The procedure to save the data is as follows.
• To save the data to an external memory device, click
Data Log
on the WindO/I-NV4
Configuration
tab to display
the
Data Log Settings
dialog box. Select a channel number to save to the external memory device and click
Edit
to display the
Individual Settings
dialog box. Select an output method check box on the
External Memory
Device
tab and configure the items. The data can be saved to the External Memory Device folder on the external
memory device. For details, refer to “External Memory Device Tab” on page 14-18.
•
To upload the data to a computer, click on
▼
to the right of
(Upload) on the toolbar in Data File Manager, and
then click the
Upload All Log Data
or
Upload Data Log Data
to open the Browser For Folder dialog box. Specify
the location to save the file and click
OK
to save the file to the specified folder. For details, refer to the Data File
Manager User's Manual.
●
Data Structure and Output Example
The data structure of the output file is as follows. The data structure for files output with batch output and real time
output is the same.
Bold items are replaced by the Data Log settings, the sampled data, the running project name, and WindO/I-NV4
version number.
*1 USB flash drive inserted in USB1 for HG2J-7U, SD memory card for HG5G/4G/3G/2G-V, HG4G/3G and HG2G-5F,
USB flash drive for HG2G-5T and HG1G/1P
*2 Only when the Header check box is selected on the Data tab in the Individual Settings dialog box
*3 Only when the Label check box is selected on the Data tab in the Individual Settings dialog box
*4 Only when the Sampling Time check box is selected on the Data tab in the Individual Settings dialog box
Headers
“Project Name”,”
Project name
”,”
Version number
”
“File Type”,”
Log type
”
“Channel No.”,”
Channel number
”
“Source”,”
Top Device Address (data number 1)
”
“Sampling Method”,”
Condition of Writing to Data Storage Area (type)
”
“
Condition of Writing to Data Storage Area (label)
”,”
Condition of Writing to Data Storage
Area (configuration details)
”
Blank row
Label row
“
Label (sampling time)
”,”
Label (data number 1)
”,”
Label (data number 2)
”... times the amount
of data
Data row
“
MM/DD/YYYY hh:mm:ss
”,
Data number 1 data value
,
Data number 2 data value
... times the
amount of data
··
·
Output example
Data size of each row
“Project Name”,”Dimmer Console”,”1.7.0.0”
- 41 bytes
“File Type”,”Data Log Data”
- 29 bytes
“Channel No.”,”1”
- 19 bytes
“Source”,”LDR100”
- 20 bytes
“Sampling Method”,”Fixed Period”
- 34 bytes
“Time[Sec]”,”1”
- 17 bytes
- 2 bytes
“Sampling Time”,”Data001”,”Data002”
- 37 bytes
“08/23/2011 18:32:04”,171,234
- 32 bytes
··
·
Summary of Contents for WindO/I-NV4
Page 1: ...B 1701 16 User s Manual...
Page 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Page 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Page 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Page 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Page 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Page 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Page 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Page 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Page 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Page 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Page 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Page 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Page 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Page 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Page 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Page 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...