3 Recipe Settings Dialog Box
18-12
WindO/I-NV4 User’s Manual
●
Channel
Tab
The
Channel
tab is used to configure the recipe name for the selected channel and the device addresses to read and
write values to.
■
Channel
Shows the block number and the channel number for the selected channel.
■
Recipe function
Selects whether or not to use the Recipe function.
■
Recipe Name
Enter the name for the Recipe function to differentiate the channel. The maximum number is 40 characters. The
default is “Recipe
n
”. (
n
: 4 digit sequential number)
■
Top Device Address
Specifies the start device address of the destination device addresses for recipe values and the source device
addresses for values of device addresses.
Click
to display the Tag Editor. For the device address configuration procedure, refer to Chapter 2 “5.1 Device
Address Settings” on page 2-70.
The specified device addresses are configured sequentially from the number 1 in
Data List
on the
Data
tab.
■
Data Type
Selects the type of data for recipe values to write and values of device addresses that are read. For details, refer to
Chapter 2 “1.1 Available Data” on page 2-1.
■
Number of Data
Specifies the number of source or destination device addresses starting with the device address configured by
Top
Device Address
.
The sequential device addresses from the start address for the number of configured device addresses is displayed in
Settings
on the
Data
tab.
The amount of data that can be set varies based on the data type. When
UBIN16(W)
,
BIN16(I)
, or
BCD4(B)
is
selected for
Data Type
, up to 8192 items of data can be configured. When
UBIN32(D)
,
BIN32(L)
,
BCD8(EB)
, or
Float32(F)
is selected, up to 4096 items of data can be configured.
■
Display Type
Selects the display type for
Data
in
Data List
configured on the
Data
tab as
Decimal
or
Hexadecimal
.
Values when saving data to a recipe file are decimal.
Block Number:
Shows the block number for the channel selected in
Settings
.
Channel Number:
Shows the channel number for the channel selected in
Settings
.
Enable:
Writes recipe values to device addresses, reads values of device addresses and saves them to
the external memory device as a recipe file.
Disable:
The Recipe function is not used.
Summary of Contents for WindO/I-NV4
Page 1: ...B 1701 16 User s Manual...
Page 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Page 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Page 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Page 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Page 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Page 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Page 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Page 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Page 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Page 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Page 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Page 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Page 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Page 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Page 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Page 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...