5 Script Coding Examples
20-60
WindO/I-NV4 User’s Manual
5.8 Data Type Designations
Script
Operation description
■
Example 5.8.1
Specify the
UBIN16(W)
as the
Data Type
on the Script Editor and the
from Lower word
as
the
Storage Method of 32-bit Numerical Data for Internal Devices
on the
System
tab in
the
Project Settings
dialog box.
[LDR 100] = 65535;
[LDR 101] = 0;
[LDR 200] = 0;
[LDR 300] = 0;
asdoubleword
{
[LDR 100] = [LDR 100]+1;
}
[LDR 200] = [LDR 100];
asdoubleword
{
[LDR 300] = [LDR 100];
}
Lower word
Upper word
Lower word
Upper word
Data Type
Device Address
UBIN32(D)
LDR100
LDR101
LDR300
LDR301
Stored value
65536
0
0
1
0
0
Stored value
65536
65536
0
1
0
1
Stored value
65536
0
1
Data Type
Device Address
UBIN16(W)
LDR100
LDR101
LDR200
Stored value
0
1
0
Stored value
0
1
0
Data Type
Device Address
UBIN16(W)
LDR100
LDR101
LDR200
LDR300
Stored value
65535
0
0
0
Lower word
Upper word
Data Type
Device Address
UBIN32(D)
LDR100
LDR101
Stored value
65535
65535
0
+1
Stores 65535 in LDR100, 0 in LDR101, LDR200 and LDR300.
Stores the value of LDR100 in LDR200.
Stores the value of LDR100 in LDR300.
Changes the Data Type to
UBIN32(D)
.
Returns the Data Type to the default
UBIN16(W)
.
Changes the Data Type to
UBIN32(D)
.
The value obtained by adding 1 to the value of the
LDR100 is stored in the LDR100 as the "UBIN32(D)".
The handling method of 32-bit numerical data follows the data storage method specified in the
Project
Settings
dialog box. For details, refer to Chapter 4 “Storage Method of 32-bit Numerical Data for Internal
Devices” on page 4-29 and Chapter 4 “Storage Method of 32-bit Numerical Data” on page 4-48.
Summary of Contents for WindO/I-NV4
Page 1: ...B 1701 16 User s Manual...
Page 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Page 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Page 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Page 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Page 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Page 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Page 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Page 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Page 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Page 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Page 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Page 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Page 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Page 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Page 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Page 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...