WindO/I-NV4 User’s Manual
3-39
5 User Communication
3
Co
m
m
un
ica
tio
n
■
Trigger Condition
Set the trigger conditions for transmission or receiving of data.
TXD
is selected as
Type
:
RXD
is selected as
Type
:
Trigger Type: A condition for data transmission is selected from the following.
Rising-edge: Data is transmitted when the value of device address changes from 0 to 1.
Falling-edge: Data is transmitted when the value of device address changes from 1 to 0.
Satisfy the condition:
Data is transmitted when the condition changes from not satisfied to satisfied.
Fixed Period: Data is transmitted at a fixed time interval.
Data Type:
Select the data type handled by the conditional expression.
Can only be set if
Satisfy the condition
is selected as
Trigger Type
.
For details, refer to Chapter 2 “1.1 Available Data” on page 2-1.
Device Address: Specifies the bit device or the bit number of the word device to serve as condition. You can only
specify the internal device.
Can only be set if
Rising-edge
or
Falling-edge
is selected as
Trigger Type
.
Click
to display the Tag Editor. For the device address configuration procedure, refer to Chapter
2 “5.1 Device Address Settings” on page 2-70.
Condition:
Sets the condition formula.
Can only be set if
Satisfy the condition
is selected as
Trigger Type
.
Click
to display the Trigger Condition Settings dialog box. For the conditional expressions
configuration procedure, refer to Chapter 2 “5.2 Setting Conditional Expressions” on page 2-73.
Period (sec):
Specify the period for command execution from 1 to 3600 (seconds).
This is enabled only when
Fixed Period
is selected in
Trigger Type
.
Trigger Type: Selects the condition to be ready to receive data from the following.
Always Enabled: The MICRO/I is always ready to receive data.
While ON:
Ready to receive data when the value of device address is 1.
Value of Device Address
1
0
Action
Execution
Execution
Execution
1
0
Value of Device Address
Action
Execution
Execution
Action
Execution
Condition
Satisfied
Not satisfied
Execution
Execution
Fixed time interval
Fixed time interval
Fixed time interval
Action
Execution
Execution
Execution
Action
Always Enabled
Value of Device Address
1
0
Enabled
Enabled
Enabled
Action
Summary of Contents for WindO/I-NV4
Page 1: ...B 1701 16 User s Manual...
Page 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Page 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Page 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Page 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Page 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Page 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Page 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Page 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Page 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Page 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Page 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Page 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Page 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Page 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Page 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Page 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...