WindO/I-NV4 User’s Manual
30-17
3 Analog I/O Modules
30
Ex
pa
ns
io
n M
od
ule
s
■
Minimum and maximum values
The values of
Min.
and
Max.
are determined by the set
Signal Type
and
Data Type
. The value is stored in the
Data
according to values of
Min.
and
Max.
.
The minimum and maximum values that correspond to the signal type and data types are as follows.
*1
Binary data (12bit)
and
Optional range (12bit)
are displayed only for FC6A-J8A1 and FC6A-J8A4.
*2
Min.
and
Max.
can be configured in the range of -32,768 to 32,767 only when
Optional range
is configured to
Data
Type
. However, when
PTC Thermistor (threshold)
is configured to
Signal Type
, the range of
Min.
and
Max.
is 100 to
10,000. For Optional range, refer to “ Optional range” on page 30-16.
*3 For details, refer to “ PTC Thermistor (Threshold)” on page 30-21.
Signal Type
Data Type
Binary data
Optional
range
Celsius
(℃)
Fahrenheit
(℉)
Resistance
(Ω)
Binary data
(16bit)
Optional
range
(16bit)
0 to 10V DC
0 to 65,535
-32,768 to 32,767
―
―
―
0 to 65,535
-32,768 to 32,767
-10 to +10V DC
-32,768 to 32,767 -32,768 to 32,767
―
―
―
-32,768 to 32,767 -32,768 to 32,767
0 to 20mA DC
0 to 65,535
-32,768 to 32,767
―
―
―
0 to 65,535
-32,768 to 32,767
4 to 20mA DC
0 to 65,535
-32,768 to 32,767
―
―
―
0 to 65,535
-32,768 to 32,767
Type K thermocouple
0 to 65,535
-32,768 to 32,767 -2,000 to 13,000 -3,280 to 23,720
―
―
―
Type J thermocouple
0 to 65,535
-32,768 to 32,767 -2,000 to 10,000 -3,280 to 18,320
―
―
―
Type R thermocouple
0 to 65,535
-32,768 to 32,767
0 to 17,600
320 to 32,000
―
―
―
Type S thermocouple
0 to 65,535
-32,768 to 32,767
0 to 17,600
320 to 32,000
―
―
―
Type B thermocouple
0 to 65,535
-32,768 to 32,767
0 to 18,200
320 to 33,080
―
―
―
Type E thermocouple
0 to 65,535
-32,768 to 32,767 -2,000 to 8,000 -3,280 to 14,720
―
―
―
Type T thermocouple
0 to 65,535
-32,768 to 32,767 -2,000 to 4,000 -3,280 to 7,520
―
―
―
Type N thermocouple
0 to 65,535
-32,768 to 32,767 -2,000 to 13,000 -3,280 to 23,720
―
―
―
Type C thermocouple
0 to 65,535
-32,768 to 32,767
0 to 23,150
320 to 41,990
―
―
―
Pt100
0 to 65,535
-32,768 to 32,767 -2,000 to 8,500 -3,280 to 15,620
―
―
―
Pt1000
0 to 65,535
-32,768 to 32,767 -2,000 to 6,000 -3,280 to 11,120
―
―
―
Ni100
0 to 65,535
-32,768 to 32,767
-600 to 1,800
-760 to 3,560
―
―
―
Ni1000
0 to 65,535
-32,768 to 32,767
-600 to 1,800
-760 to 3,560
―
―
―
NTC Thermistor
0 to 65,535
-32,768 to 32,767
-900 to 1,500
-1,300 to 3,020
―
―
―
PTC Thermistor
0 to 65,535
-32,768 to 32,767
―
―
100 to 10,000
―
―
PTC Thermistor
(threshold)
1/2/4
―
―
―
―
―
―
Ohm meter
0 to 65,535
-32,768 to 32,767
―
―
100 to 32,000
―
―
Expansion 0 to 20mA
DC
0 to 4,095
-32,768 to 32,767
―
―
―
0 to 65,535
-32,768 to 32,767
Expansion 4 to 20mA
DC
0 to 4,095
-32,768 to 32,767
―
―
―
0 to 65,535
-32,768 to 32,767
Summary of Contents for WindO/I-NV4
Page 1: ...B 1701 16 User s Manual...
Page 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Page 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Page 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Page 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Page 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Page 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Page 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Page 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Page 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Page 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Page 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Page 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...