Thermistor settings
When
NTC Thermistor
is selected as
Signal Type
for the FC6A-J8CU1 or FC6A-J8CU4, the following parameters
must be set.
The characteristic of NTC Thermistor is the resistance decreases as the temperature rises. The analog modules
measure the resistance of the thermistor and calculate the temperature based on above three parameters.
The measurable range of the resistance of NTC Thermistor is 100 Ω to 200,000 Ω. The range of temperature that can
be calculated is -90°C to 150°C. Select NTC Thermistor that functions within those ranges.
■
Data
Data refers to the input analog values converted to digital values at the interval of the sampling time.
The data is not guaranteed when the
Satus
is a value other than "0". For details on when
PTC Thermistor
(threshold) is selected as
Signal Type
, refer to “ PTC Thermistor (Threshold)” on page 30-21.
*1 When the
Sampling Time
is set to 30 milliseconds, the modules may be more easily affected by commercial power supply
noise (50/60 Hz noise) and fluctuations in input values may become larger. If there are large fluctuations in input values,
change the
Sampling Time
to 120 milliseconds.
*2 Information are described in the instruction sheet for the thermistor to use.
FC6A-J4CN1
FC6A-J4CN4
0 to 10V DC
100 msec or 10 msec
-10 to +10V DC
100 msec or 10 msec
0 to 20mA DC
100 msec or 10 msec
4 to 20mA DC
100 msec or 10 msec
Thermocouple
104 msec
Resistance thermometer
104 msec
FC6A-J4CH1Y
FC6A-J4CH4Y
Thermocouple
120 msec or 30 msec
FC6A-J8CU1
FC6A-J8CU4
Thermocouple
104 msec
NTC Thermistor, PTC Thermistor
104 msec
PTC Thermistor (threshold)
104 msec
Ohm meter
104 msec
FC6A-L06A1
FC6A-L06A4
0 to 10V DC
1 msec or 10 msec
-10 to +10V DC
1 msec or 10 msec
0 to 20mA DC
1 msec or 10 msec
4 to 20mA DC
1 msec or 10 msec
FC6A-L03CN1
FC6A-L03CN4
0 to 10V DC
100 msec or 10 msec
-10 to +10V DC
100 msec or 10 msec
0 to 20mA DC
100 msec or 10 msec
4 to 20mA DC
100 msec or 10 msec
Thermocouple
104 msec
Resistance thermometer
104 msec
Type
Signal Type
Sample Time
Parameter
Description
Range
R0
The thermistor resistance in "T0" °C (Ω)
0 to 65,535
T0
Temperature (°C)
-32,768 to 32,767
B
Thermistor B constant
-32,768 to 32,767
Summary of Contents for WindO/I-NV4
Page 1: ...B 1701 16 User s Manual...
Page 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Page 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Page 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Page 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Page 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Page 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Page 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Page 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Page 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Page 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Page 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Page 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Page 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Page 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Page 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Page 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...