1 Error Messages
36-4
WindO/I-NV4 User’s Manual
1.2 Low Battery Voltage
An internal battery maintains clock settings and log data in the MICRO/I. When the battery runs out, keep register
data, log data and other backup data will be cleared, and the contrast is reset to the default value. If this happens,
the following message is displayed when the MICRO/I is powered up, so take the indicated action.
In this case, Bit 14 (backup data error) of address 2 in System Area 2 is set, and it is reset when MICRO/I
is powered on.
The following warning messages will be displayed before the battery is dead.
In this case, the Bit 12 (Replace battery error) or Bit 13 (Replace battery error) of address 2 in the System
Area 2 is set, and it is set whenever the MICRO/I is powered on.
HG3G
HG2G-5F
HG5G-V HG4G-V
HG3G-V
HG2G-V
HG2G-5T
HG4G
HG1G HG1P
HG2J-7U
To display the warning message, in the Project Settings dialog box, on the
System Settings
tab, select the
Battery warning message
check box.
Message
Description
Backup data lost
Replace the battery.
The Log Data and Calendar Data are lost. Set the clock again.
In case of storing Keep Memory and Keep Relay to the flash memory using HMI Special Internal Relay
LSM10, stored data is transferred to the memory automatically when Backup data is lost.
Message
Description
Replace battery
The remaining battery revel is low. Replace the battery in a short time.
Replace battery
(Battery level LOW)
The remaining battery revel is lowest. Replace the battery immediately, otherwise backup
data will be lost.
Summary of Contents for WindO/I-NV4
Page 1: ...B 1701 16 User s Manual...
Page 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Page 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Page 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Page 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Page 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Page 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Page 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Page 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Page 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Page 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Page 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Page 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Page 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Page 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Page 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Page 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...