WindO/I-NV4 User’s Manual
3-83
5 User Communication
3
Co
m
m
un
ica
tio
n
Receive command: Command Settings dialog box settings
Operation for receive command
1
Change the trigger condition LM202 from 0 to 1 to be ready for receiving user communication.
2
Data is transmitted from the external device and the transmitted data is received and processed.
The receive data is as follows.
• The receive data is compared with the character data, and the value of the matching Index No. (10 (Dec)) is stored
in Index Device Address LDR230.
• The 2 bytes (specified with
Skip
) of the receive command data 43h and 44h are ignored.
• Since the Reference Device Address LDR 230 of
Device Address
of the receive command data is 10 (Dec), the
data is stored in the device address LDR250 and LDR251, which is offset by +10.
•
[STX] ABCD1234
is calculated with
BCC
of receive command data and compared with 3032h.
- When Calculation Start Position is 1 and Calculation End Position is 0: Calculates the range
STX ABCD1234
.
Item
Setting
Type
RXD
Trigger Condition
While ON, Device Address: LM202
Completed Device Address
LM203
Not Clear Completed Device
Address automatically
No
Status Device Address
LDR260
Receiving Time Out
0 (No Receive Time Out)
Comment
RXD command
Command
Data Settings dialog box
settings
Constant
(Hexadecimal)
'02'
Registering
Constant
(Character)
10: "AB", 20: "CD", Index Device Address: LDR230
Skip
2 bytes
Device Address
Conversion Type: No conversion, from Upper byte,
Number of bytes: 2, Words: 2
Device Address: LDR240, Reference Device Address: LDR230
BCC
Calculation Start Position: 1 Calculation End Position: 0, XOR
Hexadecimal to ASCII, 2 bytes
Constant
(Hexadecimal)
'0D''0A'
3
(33h)
4
(34h)
1
(31h)
STX
(02h)
2
(32h)
A
(41h)
B
(42h)
C
(43h)
D
(44h)
Skip
CR
(0Dh)
LF
(0Ah)
0
(30h)
2
(32h)
BCC
Constant
(Hexadecimal)
Device Address
Constant
(Hexadecimal)
Command settings:
Registering
Constant (Character)
Receive data:
Received data
Compare
A
(41h)
B
(42h)
Order of reception
10
LDR230:
Value of the Index Device Address
AB
10:
CD
20:
Data
Index No.
Number of
Registering
Constants: 2
(DEC)
0000h
LDR240:
0000h
LDR241:
3132h
LDR250:
Value of Device Address
LDR230=10
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
Calculation Start Position:
(5)
(4)
(3)
(8)
(7)
(6)
(2)
(1)
(0)
Calculation End Position:
3
(33h)
4
(34h)
1
(31h)
STX
(02h)
2
(32h)
A
(41h)
B
(42h)
C
(43h)
D
(44h)
CR
(0Dh)
LF
(0Ah)
0
(30h)
2
(32h)
Data used for BCC calculation
Summary of Contents for WindO/I-NV4
Page 1: ...B 1701 16 User s Manual...
Page 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Page 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Page 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Page 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Page 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Page 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Page 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Page 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Page 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Page 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Page 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Page 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Page 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Page 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Page 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Page 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...