WindO/I-NV4 User’s Manual
3-93
6 Sub Host Communication
3
Co
m
m
un
ica
tio
n
●
Monitor the error information of each Slave Number
The error information of external devices communicated with using Sub Host Communication can be monitored per
external device.
This option is configured on the
Sub Host Communication
tab in the Project Settings dialog box. Select the
Monitor the error information of each Slave Number
check box, and then specifies a word device to write the
error information. 256 word devices from top device set in this option are used. Each device is assigned to each slave
number of PLC.
Click
to display the Tag Editor. For the device address configuration procedure, refer to Chapter 2 “5.1 Device
Address Settings” on page 2-70.
●
Keep running with skipping the Slave Number of communication error
When this option is selected, skip the slave number error has occurred and connect with next slave number. This
option is configured on the
Sub Host Communication
tab in the Project Settings dialog box. Select the
Keep
running with skipping the Slave Number of communication error
check box.
When this option is not selected, retry communication with same slave number until recover from the error.
Bit
Function
Descriptions
0
Connection
Specifies the communication with the external devices of the relevant slave
number.
When this bit is 1, MICRO/I connects with each external device. When this bit
is 0, MICRO/I does not connect the external device.
Default value is 1 when the device addresses of the relevant slave number
are registered to HMI Link Registers (LLR).
1
Reserved
―
2
Finish 1st reading
This bit changes to 1 after all device addresses allocated to HMI Link
Registers (LLR) of the relevant slave number are read.
3
Reserved
―
4
Current Error
This bit changes to 1 while the communication error occurs in the device
addresses allocated to the HMI Link Registers (LLR) of the relevant slave
number. This bit changes to 0 after the communication error recovers.
5
Reserved
―
6
Error Log for Reading
This bit changes to 1 when the reading error has occurred in any device
address allocated to the HMI Link Registers (LLR) of the relevant slave
number. This bit keeps 1 even if the reading error recovers.
Writes 1 to the Bit 1 (Initialize) of the
Monitor the error information of
all Slave Numbers
check box to make this bit 0.
7
Error Log for Writing
This bit changes to 1 when the writing error has occurred in any device
address allocated to the HMI Link Registers (LLR) of the relevant slave
number. This bit keeps 1 even if the writing error recovers.
Writes 1 to the Bit 1 (Initialize) of the
Monitor the error information of
all Slave Numbers
check box to make this bit 0.
8 to 15 Reserved
―
Bit
Function
Read/Write
R
R
R
R
R/W
R
eserv
ed
Error Log f
or W
riting
Error Log f
or R
eading
R
eserv
ed
Current Error
R
eserv
ed
Finish 1st reading
R
eserv
ed
Connection
Summary of Contents for WindO/I-NV4
Page 1: ...B 1701 16 User s Manual...
Page 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Page 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Page 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Page 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Page 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Page 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Page 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Page 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Page 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Page 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Page 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Page 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Page 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Page 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Page 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Page 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...