WindO/I-NV4 User’s Manual
3-131
7 BACnet Communication
3
Co
m
m
un
ica
tio
n
●
Device Object
Use this object when the MICRO/I makes basic information available to BACnet devices.
Properties List
(1): Read and write from BACnet devices
(2): Read and write from device addresses when properties are allocated to device addresses
R: Read-only, W: Write-only, R/W: Read and write, -: Not Read and write
*1 Character encoding is ISO 10646 (UTF-8), and the maximum size is 64 bytes.
*2 Cannot be displayed on WindO/I-NV4.
Property Identifier
Data Type of Property
(1)
(2)
Comments
Object_Identifier
BACnetObjectIdentifier
R
-
Cannot be edited with WindO/I-NV4.
Object_Name
Character string
R
-
Set a fixed value with WindO/I-NV4.
Object_Type
BACnetObjectType
R
-
Cannot be edited with WindO/I-NV4.
System_Status
BACnetDeviceStatus
R
-
Cannot be edited with WindO/I-NV4.
Vendor_Name
Character string
R
-
Cannot be edited with WindO/I-NV4.
Vendor_Identifier
16-bit unsigned integer
R
-
Cannot be edited with WindO/I-NV4.
Model_Name
Character string
R
-
Set a fixed value with WindO/I-NV4.
Firmware_Revision
Character string
R
-
Cannot be edited with WindO/I-NV4.
Application_Software_Version
Character string
R
-
Set a fixed value with WindO/I-NV4.
Location
Character string
R/W
-
Set the initial value with WindO/I-NV4.
Description
Character string
R/W
-
Set the initial value with WindO/I-NV4.
Protocol_Version
Unsigned integer
R
-
Cannot be edited with WindO/I-NV4.
Protocol_Revision
Unsigned integer
R
-
Cannot be edited with WindO/I-NV4.
Protocol_Services_Supported
BACnetServicesSupported
R
-
Cannot be edited with WindO/I-NV4.
Protocol_Object_Types_Supported BACnetObjectType Supported
R
-
Cannot be edited with WindO/I-NV4.
Object_List
BACnetARRAY[N] of type
BACnetObjectIdentifier
R
-
Cannot be edited with WindO/I-NV4.
Max_APDU_Length_Accepted
Unsigned integer
R
-
Cannot be edited with WindO/I-NV4.
Segmentation_Supported
BACnetSegmentation
R
-
Cannot be edited with WindO/I-NV4.
Local_Time
Time
R
-
Cannot be edited with WindO/I-NV4.
Local_Date
Date
R
-
Cannot be edited with WindO/I-NV4.
APDU_Timeout
Unsigned integer
R
-
Cannot be edited with WindO/I-NV4.
Number_of_APDU_Retries
Unsigned integer
R
-
Cannot be edited with WindO/I-NV4.
Device_Address_Binding
BACnetLIST of type
BACnetAddressBiding
R
-
Cannot be edited with WindO/I-NV4.
Database_Revision
Unsigned integer
R
-
Cannot be edited with WindO/I-NV4.
Property_List
BACnetARRAY[N] of type
BACnetPropertyIdentifier
R
-
Cannot be edited with WindO/I-NV4.
Profile_Name
Character string
R
-
Set a fixed value with WindO/I-NV4.
Summary of Contents for WindO/I-NV4
Page 1: ...B 1701 16 User s Manual...
Page 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Page 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Page 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Page 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Page 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Page 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Page 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Page 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Page 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Page 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Page 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Page 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Page 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Page 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Page 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Page 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...