7 BACnet Communication
3-146
WindO/I-NV4 User’s Manual
Out_Of_Service
Out_Of_Service is the property that represents whether or not Present_Value and the physical input/output have
been unbound.
Out_Of_Service can be read out to an internal relay, and the status of an internal relay can be written as
Out_Of_Service.
Reliability
This property represents the reliability of the object property.
The following table shows the definition of Reliability for each object type.
YES: Valid, NO: Invalid
Reliability can be read out to a device address, and the value of a device address can be written as Reliability.
Properties
Value
Logical Value
Condition
Out_Of_Service
0
FALSE
In service (Present_Value and the physical input/output are bound.)
1
TRUE
Out of service (Present_Value and the physical input/output are unbound.)
Out_Of_Service = TRUE is used for simulations.
Definition
Value
Analog
Input
Analog
Output
Analog
Value
Binary
Input
Binary
Output
Binary
Value
no-fault-detected
0
YES
YES
YES
YES
YES
YES
no-sensor
1
YES
NO
NO
YES
NO
NO
over-range
2
YES
NO
YES
NO
NO
NO
under-range
3
YES
NO
YES
NO
NO
NO
open-loop
4
YES
YES
NO
YES
YES
NO
shorted-loop
5
YES
YES
NO
YES
YES
NO
no-output
6
NO
YES
NO
NO
YES
NO
unreliable-other
7
YES
YES
YES
YES
YES
YES
process-error
8
NO
NO
NO
NO
NO
NO
multi-state-fault
9
NO
NO
NO
NO
NO
NO
configuration-error
10
NO
NO
NO
NO
NO
NO
-- enumeration value
11 is reserved for a
future addendum
11
YES
YES
NO
YES
YES
YES
communication-failure
12
YES
YES
YES
YES
YES
YES
member-fault
13
NO
NO
NO
NO
NO
NO
monitored-object-fault
14
NO
NO
NO
NO
NO
NO
tripped
15
NO
NO
NO
NO
NO
NO
Summary of Contents for WindO/I-NV4
Page 1: ...B 1701 16 User s Manual...
Page 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Page 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Page 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Page 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Page 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Page 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Page 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Page 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Page 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Page 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Page 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Page 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Page 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Page 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Page 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Page 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...