System Area 3
This area is for changing the MICRO/I internal clock data.
Address
number
Bit
Function
Description
+3
0
Numerical input setting
complete
This bit changes to 1 when finished entering a numerical value with the
Numerical Input. This bit changes to 0 when entering a numerical value
or when entering a numerical value has been canceled. Write 1 to
numerical input setting clear (address 1, bit 10) to clear this bit.
1
Numerical input setting
cancel
This bit changes to 1 when entering a numerical value with the Numerical
Input was canceled. This bit changes to 0 when entering a numerical
value or when entering a numerical value has been completed. Write 1 to
numerical input setting clear (address 1, bit 10) to clear this bit.
2
Backlight auto off running
The value of this bit changes to 1 when
Auto OFF
is configured and the
backlight was turned off by this function. To configure
Auto OFF
, select
the
Auto OFF
check box under
Backlight
in the
Project Settings
dialog box. This bit automatically changes to 0 when the backlight turns
on.
3
Sending output to a
printer
This bit changes to 1 when sending output to the printer. This bit
automatically changes to 0 when finished sending output.
4
Transferring recipe
This bit changes to 1 when transferring recipe data. This bit automatically
changes to 0 when the transfer is finished.
5
Character input setting
complete
This bit changes to 1 when finished entering text with the Character
Input. This bit changes to 0 when entering text or when entering text has
been canceled. Write 1 to character input setting clear (address
1, bit 11) to clear this bit.
6
Character input setting
cancel
This bit changes to 1 when entering text with the Character Input is
canceled. This bit changes to 0 when entering text or when entering text
has been completed. Write 1 to character input setting clear (address
1, bit 11) to clear this bit.
7 to 15 Reserved
Address
number
Bit
Function
Description
+4
0 to 7
Clock data
Month
Enter
Month
(01 to 12) as a 2 digit BCD.
8 to 15 Clock data
Year
Enter
Year
(00 to 99) as a 2 digit BCD.
+5
0 to 7
Clock data
Hour
Enter
Hour
(00 to 23) as a 2 digit BCD.
8 to 15 Clock data
Day
Enter
Day
(01 to 31) as a 2 digit BCD.
+6
0 to 7
Clock data
Second
Enter
Second
(00 to 59) as a 2 digit BCD.
8 to 15 Clock data
Minute
Enter
Minute
(00 to 59) as a 2 digit BCD.
+7
0 to 14 Reserved
Enter 0 in the reserved area.
15
Update
Write 1 to this bit to write the entered data (address 4 to
+6, bits 0 to 15) to the MICRO/I internal clock data.
When the value of the update bit (address 7, bit 15) becomes 1, the clock data is updated as a
whole.
Year, month, day, hour, minute, and second cannot be set individually.
Summary of Contents for WindO/I-NV4
Page 1: ...B 1701 16 User s Manual...
Page 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Page 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Page 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Page 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Page 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Page 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Page 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Page 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Page 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Page 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Page 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Page 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Page 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Page 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Page 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Page 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...