3 Project Settings Dialog Box
4-44
WindO/I-NV4 User’s Manual
• When using the MICRO/I as UDP, the MICRO/I cannot automatically identify and reply to the IP address
and port number of the external device. UDP broadcasting is also not supported.
• For TCP client and TCP server, make a 1:1 connection between the MICRO/I and the external device for
one user communication setting.
• When the
Change IP Address and Port Number by Device Address
check box is selected, the
changed IP address and port number are reflected when data is next sent.
• Regarding TCP port number of MICRO/I, note the following points.
The numbers that cannot be used: - 2539: Maintenance communication (Data Transfer)
- 2538: For pass-through
- 2101: For FC4A Series MicroSmart direct connection pass-through
Duplicate numbers cannot be configured in the following functions:
- Maintenance communication
(
refer to “Port Number” on page 4-41)
- Web server function (
refer to “Port Number” on page 4-67)
- FTP server function (
refer to “Port Number” on page 4-68)
-
TCP Server
is selected for the User Communication
(
refer to “Port No.” on page 4-43)
-
Modbus
as
Manufacture
and
Modbus TCP Server
as
Communication Driver
are selected on the
Communication
Driver
tab
(
refer to the WindO/I-NV4 External Device Setup Manual)
-
YASKAWA Electric
as
Manufacture
and
MP2000(Ethernet)
as
Communication Driver
are selected on the
Communication
Driver
tab
(
refer to the WindO/I-NV4 External Device Setup Manual)
• Duplicate UDP port numbers of MICRO/I cannot be configured in the following functions.
-
UDP
is selected for the User Communication (
refer to “Port No.” on page 4-43)
-
IDEC System
as
Manufacture
and
DM LINK Ethernet(UDP)
as
Communication Driver
are
selected on the
Communication Driver
tab
(
refer to the WindO/I-NV4 External Device Setup Manual)
-
OMRON
as
Manufacture
and
SYSMAC CS1/CJ series(Ethernet)
as
Communication Driver
are
selected on the
Communication Driver
tab
(
refer to the WindO/I-NV4 External Device Setup Manual)
• The connection status for TCP clients and the TCP server can be checked with the value of the HMI
Special Data Registers (LSD). The connection is disconnected when 0. The connection is connected when
1.
LSD67-0: Connection status for User Communication 1 set to Ethernet interface
LSD67-1: Connection status for User Communication 2 set to Ethernet interface
LSD67-2: Connection status for User Communication 3 set to Ethernet interface
• To forcibly disconnect the connection with TCP clients and the TCP server, set the value of the HMI Special
Data Registers (LSD) from 0 to 1.
LSD68-0: User Communication 1 set to Ethernet interface
LSD68-1: User Communication 2 set to Ethernet interface
LSD68-2: User Communication 3 set to Ethernet interface
Summary of Contents for WindO/I-NV4
Page 1: ...B 1701 16 User s Manual...
Page 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Page 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Page 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Page 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Page 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Page 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Page 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Page 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Page 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Page 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Page 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Page 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Page 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Page 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Page 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Page 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...