3 Project Settings Dialog Box
4-82
WindO/I-NV4 User’s Manual
■
Time Zone
Select the time zone to set. (Default: (UTC) Coordinated Universal Time)
●
Checking the communication contents with the SNTP server
You can check the communication contents with the SNTP server through the values of the HMI Special Internal
Relays and the HMI Special Data Registers.
■
LSM57
When the value of this bit changes from 0 to 1, get the current time from the SNTP server. The acquired current time
is written to the MICRO/I internal clock and stored in the MICRO/I internal current time data (LSD13 to 19).
■
LSD29
The execution result of communication with the SNTP server is stored.
■
LSD30
The elapsed time (0 to 65535 minutes) from the time last obtained from the SNTP server to the current time is stored.
If the current time is successfully obtained, the value will be reset and the elapsed time will start counting. Even if it
fails to get the current time, the elapsed time counting continues without interruption until it succeeds.
Enable Daylight Saving Time: Select this check box to correct the time to daylight saving time when it exists in the
selected time zone.
Start: Displays the start date and time of daylight saving time.
End: Displays the end date and time of daylight saving time.
When the Enable Daylight Saving Time check box is selected, the following date and time in the Alarm Log,
Data Log, and Operation Log functions may appear to log data at the same time twice, or to have
advanced in time and no data has been logged. This is due to the daylight saving time correction.
• Date and time when output as a CSV file
• Output date and time added to the CSV file name
• Date and time displayed on the part
• The daylight saving time system is subject to change, therefore check the dates and times displayed in
Start and End.
• IANA Time Zone Database version number 2019a is adopted.
Status
Cause
0: Successfully Completed
-
2: Timeout error
The SNTP server does not return a response after the timeout period (30 seconds) has
elapsed due to the following reasons.
• An Ethernet cable is disconnected.
• Host Name of the SNTP server is incorrect.
• IP address of the SNTP server is incorrect.
• A connection cannot be made to the preferred DNS server and alternate DNS server.
4: Other error
MICRO/I cannot perform communication with SNTP server
Summary of Contents for WindO/I-NV4
Page 1: ...B 1701 16 User s Manual...
Page 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Page 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Page 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Page 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Page 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Page 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Page 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Page 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Page 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Page 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Page 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Page 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Page 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Page 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Page 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Page 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...