7 Alarm List Display
10-138
WindO/I-NV4 User’s Manual
7.3 Properties of Alarm List Display Dialog Box
This section describes items and buttons on the properties dialog box.
●
General
Tab
■
Part Name
Enter a name for the part. The maximum number is 20 characters.
■
Message Settings
Selects the method for switching message to display.
The active alarm messages are displayed.
Use Alarm Log Settings:
Displays messages for the active alarms. The alarms are configured by the Alarm Log
settings.
Alarm Log Settings:
Displays the
Alarm Log Settings
dialog box.
New Message List:
Displays the messages registered in Text Manager according to the state of bits in the
trigger device address configured on the
List
tab.
Example: When
Use Alarm Log Settings
is selected, the source device address (device address to monitor)
configured by the Alarm Log function is D0, and the following messages are allocated to the channels
D0-0
:
D0-1
:
D0-2
:
D0-3
:
ID1
Current fault
ID2
ID3
ID4
Pump fault
High pressure
Low air pressure
Message
Source device address
Message to display
Bit state of Source device address
D0-0
Display ID1
Action
Display ID2, ID3
1
0
1
1
0
D0-1
0
1
0
1
0
D0-2
0
1
1
1
0
D0-3
0
0
1
1
0
No message
Display ID1, ID2,
ID3, ID4
Display ID1, ID3,
ID4
Current fault
Pg. Up
Pg. Dwn
Pg. Up
Pg. Dwn
Pump fault
High pressure
Pg. Up
Pg. Dwn
Current fault
High pressure
Low air pressure
Pg. Up
Pg. Dwn
Current fault
Pump fault
High pressure
Low air pressure
Pg. Up
Pg. Dwn
If all bits in the device address are 0 or if a bit with no
associated message becomes 1, display nothing.
Summary of Contents for WindO/I-NV4
Page 1: ...B 1701 16 User s Manual...
Page 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Page 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Page 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Page 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Page 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Page 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Page 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Page 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Page 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Page 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Page 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Page 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Page 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Page 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Page 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Page 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...