3 Alarm Log Settings Dialog Box
13-16
WindO/I-NV4 User’s Manual
●
Channel
Tab
The
Channel
tab is used to configure the device addresses to monitor and the alarm detection condition.
■
Source Device Address Type
Selects the type of device address to monitor.
■
Number of Blocks
Configures the Alarm Log data in block units. The number of blocks that can be set varies based on the
Source
Device Address Type
setting.
■
Reference Screen
Select the type of reference screen from the following items.
Base Screen
,
Popup Screen
,
Not Use
The reference screen is displayed when a message is selected on the Alarm List Display or the Alarm Log Display and
the key button
Ref.
is pressed. It is the base screen or popup screen associated with each channel.
Word: Uses a word device. Device Addresses are configured per block.
Bit:
Uses a bit device. Device Addresses are configured per channel.
Word: 0 to 128
Bit:
0 to 8
1 block is composed of 16 channels. 1 device address can be monitored for each channel. The maximum
number of device addresses that can be monitored is 16 for each block.
Reference screen
2. Press the key button
Ref.
Reference screen opens
Up
Down
Delete
Select
Reference
Occurrence Message Recovered Confirmed
12/01 09
:
15 Motor
fault
12/01 10
:
02 Pump1
fault
12
:
50
12/01 10
:
28 High
pressure
12
:
54
12/01 13
:
02 Pump1
fault
Up
Down
Delete
Select
Reference
Occurrence Message Recovered Confirmed
12/01 09
:
15 Motor
fault
12/01 10
:
02 Pump1
fault
12
:
50
12/01 10
:
28 High
pressure
12
:
54
12/01 13
:
02 Pump1
fault
1. Select a message displayed
on the Alarm List Display
or the Alarm Log Display
Pump 1 fault
Pump 1 output low
Stop
Start
Press Stop, check the air,
then press Start.
Air Press.
kg/m
2
0000
Key button
Ref.
Summary of Contents for WindO/I-NV4
Page 1: ...B 1701 16 User s Manual...
Page 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Page 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Page 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Page 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Page 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Page 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Page 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Page 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Page 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Page 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Page 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Page 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Page 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Page 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Page 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Page 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...