3 Recipe Settings Dialog Box
18-8
WindO/I-NV4 User’s Manual
This section describes the items and buttons on the
Recipe Settings
dialog box and the
Individual Settings
dialog
box.
3.1 Recipe Settings Dialog Box
Use the
Recipe Settings
dialog box to collectively manage the save destination of data for recipes, the device
addresses for writing recipe values and reading values of device addresses, and those execution conditions.
■
Number of Blocks
The operation using the data for the recipe is configured in blocks (0 to 64). 1 channel is used for 1 item of data for
the recipe. 1 block is 16 channels.
The maximum number of blocks that can be configured is 64 blocks. The maximum number of device addresses that
can be configured for 1 channel is 8192 devices.
■
Settings
Edits the recipe settings for each channel.
3
Recipe Settings Dialog Box
HG3G
HG2G-5F
HG5G-V HG4G-V
HG3G-V
HG2G-V
HG2G-5T
HG4G
HG1G HG1P
HG2J-7U
No.:
Displayed as (Block No.)-(Channel No.). Double clicking the cell displays the
Individual
Settings
dialog box. For details, refer to “3.2 Individual Settings Dialog Box” on page 18-10.
Access to:
Shows the save destination for the data for the recipe. Double clicking the cell switches between
Internal Memory
and
External Memory Device
.
Trigger Setting:
Shows the operation using the data for the recipe. When
External Memory Device
is selected
for
Access to
, double clicking the cell switches between
Write-only
,
Read/Write
, and
Read-
only
. Shows
Write-only
when
Internal Memory
is selected for
Access to
.
Read Trigger:
Shows the device address that triggers saving the recipe file. Double clicking the cell displays
the Tag Editor. For the device address configuration procedure, refer to Chapter 2 “5.1 Device
Address Settings” on page 2-70.
This option can only be configured when
Read/Write
or
Read-only
is selected under
Trigger
Setting
.
Write Trigger:
Shows the device address that triggers writing recipe values to device addresses. Double
clicking the cell displays the Tag Editor. For the device address configuration procedure, refer to
Chapter 2 “5.1 Device Address Settings” on page 2-70.
This option can only be configured when
Read/Write
or
Write-only
is selected under
Trigger Setting
.
Recipe function:
Shows whether or not to use the Recipe function. Double clicking the cell switches between
Enable
and
Disable
.
Summary of Contents for WindO/I-NV4
Page 1: ...B 1701 16 User s Manual...
Page 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Page 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Page 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Page 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Page 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Page 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Page 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Page 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Page 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Page 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Page 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Page 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Page 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Page 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Page 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Page 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...