Completed Device Address:
Specify the bit device or the bit number of the word device for reporting that data transmission or receiving was
successfully completed. You can only specify an internal device.
Click
to display the Tag Editor. For the device address configuration procedure, refer to Chapter 2 “5.1 Device
Address Settings” on page 2-70.
Example: When
Trigger Type
in
Trigger Condition
is
While ON
,
Device Address
is LM100 and
Completed
Device Address
is LM101
When data receiving is successfully completed, the value of the Completed Device Address LM101
changes to 1. When the value of the Trigger Condition device address LM100 changes from 0 to 1, the
value of the Completed Device Address LM101 changes to 0.
Not Clear Completed Device Address automatically:
Select this check box when the value of the Completed Device Address is not set to 0 automatically after it
changes to 1. This can be configured when
RXD
is selected as
Type
.
Example: When
Trigger Type
in
Trigger Condition
is
While ON
,
Device Address
is LM100 and
Completed
Device Address
is LM101
When the
Not Clear Completed Device Address automatically
check box is not selected:
When data receiving is successfully completed, the value of the Completed Device Address LM101
changes to 1. When the first data of the next frame is received, the value of the Completed Device
Address LM101 changes to 0.
When the
Not Clear Completed Device Address automatically
check box is selected:
When data receiving is successfully completed, the value of the Completed Device Address LM101 is set
to 1. Even after the first data of the next frame is received, the value of the Completed Device Address
LM101 does not change to 0.
Value of Completed Device Address
LM101
Receive command
Value of Device Address LM100 when
Trigger Condition is
While ON
1
0
1
0
Receive data 1 frame
Value of Completed Device Address
LM101
Receive command
Value of Device Address LM100 when
Trigger Condition is
While ON
1
0
1
0
Receive data 1 frame
Receive data 1 frame
1
0
1
0
Receive data 1 frame
Receive data 1 frame
Value of Completed Device Address
LM101
Receive command
Value of Device Address LM100 when
Trigger Condition is
While ON
Summary of Contents for WindO/I-NV4
Page 1: ...B 1701 16 User s Manual...
Page 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Page 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Page 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Page 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Page 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Page 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Page 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Page 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Page 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Page 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Page 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Page 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Page 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Page 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Page 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Page 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...