2 HG5G/4G/3G/2G-V
35-20
WindO/I-NV4 User’s Manual
■
Performance Specifications
■
EMC Specifications
*1 Please be aware that small black and bright dots might show up on LCD Screen: it is not a failure or malfunction.
*2 The life of the LCD itself at an ambient temperature of 25°C. This is not a guaranteed value. The actual life depends on the
environment and conditions of use.
*3 It is a protection structure for the operating surface of HMI, which is attached to a panel. Although protection structure
suffices every test conditions, it does not guarantee to operate under all of the environmental condition.
As for IP66F/IP67F oilproof structure, it suffices oilproof test conditions. Conditions are listed in the document that comes
with Japanese Industrial Standard JIS C 0920.
Protection structure do not gurantee usage under long exposure to oil or usage of oil that is not prescribed in the document.
Please test/check beforehand to avoid trouble.
Type No.
HG5G-V
HG4G-V
HG3G-VA
HG3G-V8
HG2G-V
Display
LCD Type
TFT color LCD
(TN Type)
TFT color LCD (IPS Type)
TFT color LCD
(TN Type)
Display Colors
65536 Colors
Effective Display Area 304.1 (W) ×
228.1 (H) mm
245.76 (W) ×
184.32 (H)
mm
210.4 (W) ×
157.8 (H)
mm
170.496 (W) ×
127.872 (H)
mm
115.2 (W) ×
86.4 (H) mm
Display Resolution
1024 (W) × 768 (H) dots
640 (W) ×
480 (H) dots
View angle
Left/Right/Bottom: 80°,
Top: 60°
Left/Right/Top/Bottom: 85°
Left/Right/Top/
Bottom: 80°
Brightness of LCD only 650 cd/m
2
600 cd/m
2
700 cd/m
2
800 cd/m
2
800 cd/m
2
Brightness Adjustment 48 levels
Backlight
LED
Backlight Life
Approx. 100,000 hours (The time until brightness becomes 50% of the initial value)
Touch
Panel
Switch Type
Analog Resistive Film
Operating Force
3N maximum
Multiple Operations
Impossible
Life
1,000,000 operations
User Memory
Approx. 58 MB
Backup Battery
Coin type lithium manganese dioxide battery CR2032W
Guarantee Period: 1 Year (Operating Temperature at 25°C)
Recommended Replacement Span: Every 5 Years (Operating Temperature at 25°C)
Backup Data
Calendar, Log Data, HMI Keep Relays, HMI Keep Registers
Buzzer output
Single tone (tone length is adjustable)
Degree of Protection
IP66F, IP67F (IEC60529)
TYPE 4X
TYPE 13
Weight (approx.)
3.2kg
2.1kg
1.65 kg
1.25 kg
0.65 kg
Radiated Emission
Class A : 10m
40dBµV/m quasi-peak (30M to 230MHz)
47dBµV/m quasi-peak (230M to 1GHz)
Electrostatic Discharge
Contact : ±6kV Air : ±8kV
Electromagnetic Field
10V/m (80M to 1.0GHz)
3V/m (1.4G to 2.0GHz)
1V/m (2.0G to 2.7GHz)
80% AM (1kHz)
Fast Transient Burst
Power : ±2kV Communication cable : ±1kV
Surge Immunity
±500V (b24V and 0V) ±1kV (b24V and FE, 0 and FE)
Conducted Radio
Frequency Immunity
3V (Power, Communication cable) (150k to 80MHz)
80% AM (1kHz)
Summary of Contents for WindO/I-NV4
Page 1: ...B 1701 16 User s Manual...
Page 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Page 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Page 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Page 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Page 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Page 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Page 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Page 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Page 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Page 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Page 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Page 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Page 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Page 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Page 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Page 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...